Paul Industries provides boiler repair in Missouri for manufacturing plants, hospitals, universities, food and animal health producers and commercial buildings, repairing watertube, firetube, cast iron and electric boilers and planning every pressure part repair around the state’s inspection certificate rules. Missouri regulates boilers through the Boiler and Pressure Vessel Act, sections 650.200 to 650.290 of the Revised Statutes, and the Division of Fire Safety’s rules at 11 CSR 40-2, which decide who inspects the repair, when the certificate is due and when a permit comes first. Paul Industries is headquartered at 256 Shore Drive, Kilmarnock, Virginia, and takes boiler work across Missouri and in all 50 states.

Request a quote or call 201-450-8280

Headquarters 256 Shore Drive, Kilmarnock, Virginia
State program Division of Fire Safety, Boiler and Pressure Vessel Unit (RSMo 650.200 to 650.290)
Power boilers Certificate inspection every year, plus an annual external check (11 CSR 40-2.022)
Heating boilers Certificate inspection every two years (RSMo 650.260)
Welded repairs National Board R program, to the NBIC or API 510 (11 CSR 40-2.065)
Reviewed November 2026

What the Missouri boiler code requires of a repair

The Missouri boiler code is a short statute plus a set of adopted national documents: section 650.215 directs the Board of Boiler and Pressure Vessel Rules to adopt the ASME Boiler and Pressure Vessel Code for new construction and to base repair rules on the National Board Inspection Code (NBIC) or API 510. Rule 11 CSR 40-2.015 names the editions in force: the 2019 ASME Code, the 2019 NBIC with Parts 1 and 3 mandatory and Part 2 permissive, ASME B31.1 (2018) for boiler proper and boiler external piping, ASME CSD-1 (2018), NFPA 85 (2019) and NFPA 54 for fuel gas piping.

For a repair, rule 11 CSR 40-2.065 is the operative text. A welded repair to a boiler, including welding an attachment to the pressure boundary, is made under a National Board R Certificate of Authorization and conforms to the NBIC, or to API 510 where that code applies. An alteration, which the rules define to include nonphysical changes such as a higher maximum allowable working pressure, falls under the same R program with alterations in its scope. Safety and safety relief valves are repaired only under a National Board VR Certificate of Authorization, and nobody may adjust a relief device to hold a pressure above the one printed on the inspection certificate.

Paul Industries treats those requirements as the frame for the job rather than paperwork at the end. Before a boiler is opened, the scope is sorted into maintenance (gaskets, refractory patches, burner parts, controls), welded repair, alteration and valve work, and the inspector is consulted on anything in the last three groups. The national picture of failure modes and repair methods is on the boiler repair service page; this page covers what Missouri adds.

Is your boiler under the state program, a city ordinance or neither?

Missouri’s boiler act reaches every fired and unfired steam boiler, hot water heating boiler, hot water supply boiler and pressure vessel in the state, under section 650.200, unless section 650.230 exempts it or a city or charter county runs its own program. Section 650.290 states that the act does not apply in a city or chartered county that regulates boilers or pressure vessels by ordinance, so the first question on any job is which authority holds the boiler’s records.

Which Missouri boilers sit outside the state inspection program
Equipment or settingStatutory basisWhat it means for a repair
Boilers in a city or charter county with its own boiler ordinanceRSMo 650.290The ordinance and its inspector govern; Paul Industries plans the repair to that program’s forms and notices
Boilers under federal control or inspected by another federal or state agencyRSMo 650.230.1(1)The controlling agency’s inspection rules apply
Boilers on farms used solely for agricultural purposesRSMo 650.230.1(7)No state certificate; the repair is still made to the code of construction
Boilers and vessels in canneries used solely for canningRSMo 650.230.2(1)Exempt from the inspection and fee sections 650.260 to 650.275
Low-pressure heating boilers in homes and apartment houses of fewer than six familiesRSMo 650.230.2(2) and (3)Exempt from state inspection within the pressure limits stated
Hobby and miniature boilersRSMo 650.230.1(8) and 650.230.2(4)Outside commercial and industrial work

Every other boiler at a plant, hospital, school, office building or warehouse carries a state serial number and an inspection certificate. Rule 11 CSR 40-2.022 requires each object to be stamped “MO” followed by its state number, or to carry a metal tag at least one inch by four inches, placed as close to the ASME nameplate as practical. That number is how the inspector, the insurer and the repair records find the boiler, so Paul Industries photographs the tag and the nameplate on the first visit.

Missouri boiler inspection intervals under section 650.260

Missouri boiler inspection intervals depend on whether the boiler is a power boiler or a heating boiler, as section 650.205 defines them: a power boiler makes steam above 15 psig, or is a water boiler above 160 psig or 250 degrees Fahrenheit, and a heating boiler stays at or below those limits. Section 650.260 then sets the cycle: power boilers receive a certificate inspection every year and an external inspection under pressure every year, while low-pressure steam, hot water heating and hot water supply boilers receive a certificate inspection every two years.

Missouri state boiler inspection requirements by boiler type
BoilerCertificate inspectionRule detail
Power boiler, steam above 15 psigEvery year, internal where construction permitsPlus an annual external inspection under normal operating conditions (11 CSR 40-2.022(3))
Single power boiler over 400,000 lb/hInternal every two yearsFull-time operators, water chemistry documented at least weekly, NBIC welding and an annual external, verified each year
Coil-type steam generator, waste heat boiler with welded headsExternal every year while runningInternal inspection only if the inspector requires it
Steam heating boiler, 15 psig or lessEvery two yearsInternal where construction permits
Hot water heating or supply boiler over 30 years oldInternal every two yearsWhere construction permits; otherwise as complete as possible in operation
Hot water heating or supply boiler 30 years old or lessExternal every two yearsInspector may order an internal inspection
Water heaters and fired jacketed steam kettlesExternal every two yearsSame biennial cycle as heating boilers

People asking how often do boilers need to be inspected in Missouri therefore get two answers: yearly for power boilers and every two years for heating boilers, with a 30-day grace period past the certificate’s expiry for the inspector under the rule, and the chief inspector able to vary the frequency on documented service conditions. The age trigger matters for repair planning: a hot water boiler that passes its thirtieth year moves from an external to an internal inspection, and that first internal opening often finds tube and section wear that drives a repair.

Who inspects the repair: the Missouri state boiler inspector or the insurer?

A boiler without boiler and machinery insurance is inspected by the chief inspector or a deputy inspector employed by the Department of Public Safety, which is what owners mean by the Missouri state boiler inspector. A boiler covered by an insurance policy is inspected by a special inspector employed by the insurance company and commissioned under section 650.245, and its owner pays no state inspection fee, only the certificate fee.

The difference shapes the repair schedule in three ways. The insurer’s inspector usually sets the internal inspection date with the plant, so a repair found at that opening runs into the same outage. A certificate issued on a special inspector’s report becomes invalid under section 650.265 once the insurance ceases, so a change of carrier during a repair needs a fresh look at the certificate. And rule 11 CSR 40-2.022 requires insurers to tell the chief inspector within seven days when they suspend coverage for an unsafe condition, which often arrives at the plant as the first sign that a repair is no longer optional.

Either inspector can suspend a certificate when a boiler cannot run without menace to public safety. Section 650.270 makes running a boiler without a valid certificate, or above the pressure on the certificate, a class A misdemeanor, with each day a separate offense. Paul Industries plans a repair so the boiler goes back on line with a current certificate, which usually means the inspector sees the finished weld, witnesses or accepts the pressure test and issues the paperwork before firing.

Preparing a Missouri boiler for the inspection that leads to a repair

Missouri puts the preparation for an internal inspection on the owner, and rule 11 CSR 40-2.022(8) lists it in detail: drain and wash the boiler, remove manhole and handhole plates and washout plugs, cool and clean the furnace, open insulation or brickwork where the inspector asks, and remove or disassemble every low-water fuel cutoff. On a boiler tied to a common header, the nonreturn and steam stop valves are closed, tagged and padlocked with the drain between them open, and the feed and blowoff valves are treated the same way.

An inspector may decline a boiler that is not ready, and the certificate is then voided or held until it is, with an hourly reinspection charge. Canceling a prearranged internal inspection takes at least 24 hours’ notice. Paul Industries prepares boilers to that list as part of the outage scope, so the inspection, the findings and the repair happen in one opening: the boiler is drained, opened and cleaned by the repair team, the inspector writes the findings, and the tubes, gaskets and refractory needed for the most likely findings are already on site.

When is a Missouri boiler installation permit required?

A Missouri boiler installation permit is required before work starts on every new, second-hand or reinstalled boiler, and rule 11 CSR 40-2.025 treats the replacement or relocation of an existing boiler as a new installation. The installer applies to the Division of Fire Safety’s Boiler and Pressure Vessel Unit at least 60 days before the installation starts, the chief inspector may require a plan review at $35 an hour up to $500, and a copy of the permit stays at the site.

Repairs to an existing boiler in place do not need an installation permit, but a repair that turns into a replacement does, and that is where schedules slip. The rule waives the advance permit for an emergency replacement after a failure, on notice to the chief inspector, with the application filed within seven calendar days of the start of work. Permit fees run $70 for units of 400,000 Btu per hour or less, $175 up to 12,500,000 Btu per hour and $245 above that. When a boiler repair or replacement decision is close, Paul Industries files the permit application early so the replacement route stays open without a 60-day wait.

A used boiler brought in from another site is a second-hand object under rule 11 CSR 40-2.062: it needs the chief inspector’s approval before installation, ASME construction with its manufacturer’s data report, and a certificate inspection before it runs. A non-ASME boiler can be reinstalled only when it moves from one Missouri location to another.

Controls, burners and boiler external piping under the Missouri rules

Burner and control repairs on Missouri power boilers are measured against two adopted standards, chosen by heat input under rule 11 CSR 40-2.030: boilers under 12,500,000 Btu per hour contracted after January 1, 2004 meet ASME CSD-1, while single boilers at or above that input, pulverized fuel boilers and waste heat boilers meet NFPA 85. The same rule makes any modification or replacement of controls on an existing boiler after January 1, 2004 meet the requirements for a new installation.

That clause turns a routine flame safeguard or low-water cutoff replacement into an upgrade on older boilers. A burner management system replaced on a 1990s watertube boiler takes on NFPA 85 purge, supervision and trip logic; a replaced operating control on a smaller packaged boiler takes on CSD-1 limit and cutoff arrangements. Paul Industries scopes those upgrades with the repair, tests the trips and records the results for the inspector, and pairs fuel train work with the NFPA 54 or NFPA 31 requirements for gas and oil.

Boiler external piping, from the boiler to the first stop valve, is part of the boiler under the rule and is built to ASME Section I and B31.1. Safety valve outlets are piped to a safe discharge with no valve in the inlet or outlet, weighted-lever valves and cast iron seats or disks are prohibited, and blowoff tanks are built to ASME Section VIII Division 1. Piping beyond the stop valve is covered on the process piping in Missouri page, and the welding practice behind both on the industrial welding services in Missouri page.

Missouri regions and the boilers they run

Boiler repair across Missouri follows the state’s industrial map: hospital, university and manufacturing plants in Greater St. Louis, food, animal health and automotive plants around Kansas City, and food processing, manufacturing and institutional heating in Springfield, Joplin, Columbia, Jefferson City, St. Joseph and Cape Girardeau. Each region has its own heating season and outage calendar.

Missouri regions, typical boiler plants and repair planning
RegionTypical boiler plantsRepair planning emphasis
St. Louis and St. Louis CountyHospital and university central plants, breweries, chemical and life sciences plants, office towersConfirming city or county ordinance coverage, shoulder-season outages, steam to sterilizers and humidifiers
St. Charles County and WentzvilleAutomotive paint and process heat, distribution and manufacturing plantsRepairs timed to model changeovers and planned shutdown weeks
Kansas City and the NorthlandAnimal health and pet food plants, food processing, automotive assembly, government and campus heatingProcess steam continuity, sanitation loads, colder January nights than St. Louis
St. JosephAnimal health manufacturing, food and grain processingClean and plant steam for regulated production, outages planned with the quality unit
Columbia and Jefferson CityUniversity, hospital and state government heating plantsCampus outages between terms, public-works wage rules on state projects
Springfield, Joplin and southwest MissouriFood processing, manufacturing and hospital plantsWashdown and cooking steam, boilers sized for production peaks
Cape Girardeau and the BootheelConsumer products, food and agricultural processingFarm exemption checks for agricultural boilers, harvest-season loads

Boiler repair, St. Louis, MO and St. Louis County

Greater St. Louis has the state’s densest population of large heating plants and process steam users, and its winter sets the outage window. St. Louis averages a January low of 24 degrees Fahrenheit and has about 19 days a year when the temperature stays below freezing all day (NOAA normals, 1991 to 2020), so a steam boiler St. Louis hospitals depend on is repaired between April and October unless redundancy covers a winter outage. Boiler service St. Louis owners schedule in summer covers the internal inspection opening, tube cleaning, low-water cutoff and safety valve checks, and combustion tuning. Because the city and county jurisdictions in the region set many of their own building rules, Paul Industries confirms at the start whether the boiler’s certificate sits with the state program or with a municipal ordinance.

Boiler repair, Kansas City and western Missouri

Kansas City runs slightly colder, with a January low of 20 degrees and about 26 days a year that stay below freezing, and its boiler population is weighted toward process plants: animal health and pet food production, food processing and automotive assembly. Boiler repair Kansas City process plants schedule usually follows the production calendar rather than the heating season, and boiler service Kansas City owners buy often bundles the annual power boiler inspection with burner tuning and water treatment review. Plants that straddle the state line keep Missouri and Kansas boilers on separate certificate cycles under separate laws.

Process steam at Missouri’s animal health, food and automotive plants

Missouri’s process boilers carry production loads that cannot wait for a mild week. Boehringer Ingelheim runs a large animal health manufacturing campus in St. Joseph, where vaccine and drug production use plant steam for sterilization, clean steam generation and building heat, and the Kansas City region anchors an animal health corridor of more than 300 companies. General Motors announced a $157 million investment at its Wentzville Assembly plant in July 2026 that centers on refurbishing the paint shop, an area where hot water and steam heat drive pretreatment and curing.

Repairs at plants like these are planned against production campaigns and quality records. A boiler that feeds a clean steam generator or an autoclave is part of a qualified utility chain, so its repair is recorded so the quality unit can show the steam supply was restored to its qualified state; the qualification side is covered on the validation and commissioning in Missouri page. Receivers, blowdown tanks and deaerator vessels that need replacement during the same outage are built under the pressure vessel fabrication in Missouri page’s scope, and condensate and feedwater tanks under tank fabrication in Missouri.

Old boilers, nonstandard boilers and the 30-year rule

Missouri treats boilers that carry no ASME stamp as nonstandard, and rule 11 CSR 40-2.030 limits a nonstandard power boiler installed before November 12, 1986 to a 30-year service life unless the chief inspector extends it. An extension needs a maximum allowable working pressure recalculated with an allowable stress of no more than 22 percent of the material’s tensile strength, a pressure test every two years held for at least 30 minutes, and every safety device the ASME Code requires installed and working.

ASME-stamped boilers of any age have no fixed service life under the rule, provided they pass inspection. For both kinds, the age of a boiler decides how much of the repair estimate goes to hidden conditions: tube sheets thinned by decades of blowdown, refractory anchors rusted through, and controls that predate CSD-1. The weighing of boiler repair or replacement on an older unit therefore includes the permit timeline above, the clearance rule for boilers installed or reinstalled on or after January 1, 2010 (at least 36 inches on each side, 48 inches between boilers in a battery and 84 inches above a top manhole) and whether a new boiler fits the room without moving walls.

How state fees and outage scope set the price of boiler repair in Missouri

The cost of boiler repair in Missouri is set by the repair scope and the outage, with the state’s own fees a small share. Under rule 11 CSR 40-2.022, the state’s boiler inspection cost for an internal power boiler inspection runs $125 to $195 by capacity, an external inspection $85 or $110, an external heating boiler inspection $70, and each inspection certificate $40; hourly work is billed at $100 an hour up to eight hours. Boilers covered by insurance are inspected by the insurer’s special inspector instead, without the state inspection fee.

The repair price itself is driven by the number of tubes or sections involved and how they are reached, refractory and casing work, burner and control parts, any control upgrade the 2004 rule triggers, nondestructive examination, the pressure test, insulation and the documentation. Temporary steam or heat, rental boiler permits and overtime to finish before cold weather belong in the estimate too. Public projects add Missouri’s prevailing wage: section 290.230 requires the prevailing hourly rate on public works construction, exclusive of maintenance work, and the Division of Labor Standards treats projects of $75,000 or less as outside the law. Paul Industries prices a repair from the nameplate data, the latest inspection report and photographs, gives a budget range from comparable scope, and fixes the price once the boiler is open.

Who repairs process and heating boilers in Missouri?

Paul Industries repairs boilers in Missouri, from cast iron sectional and packaged firetube heating boilers in commercial buildings to watertube power and process boilers at food, animal health, automotive, chemical and university plants. Paul diagnoses trips and leaks, replaces and plugs tubes, retubes firetube boilers, replaces sections, repairs refractory and casings, rebuilds burners and fuel trains, replaces low-water cutoffs, flame safeguards and burner management systems, tests controls to CSD-1 or NFPA 85, and installs replacement boilers with their external piping and controls.

Among steam boiler repair companies, the one that also prepares the boiler for the inspector, plans the welded work under the NBIC and the National Board R program, files the installation permit when a repair becomes a replacement and hands over the records the certificate depends on keeps a Missouri outage to one opening. Paul Industries takes that whole sequence under one contract. Paul is headquartered in Kilmarnock, Virginia, where it repairs boilers across its home state (see boiler repair in Virginia), and the neighboring boiler repair in Illinois page covers the rules across the Mississippi. Missouri work runs under the same East Coast contract structure that covers the Midwest and all 50 states.

Paul Industries on Missouri boiler outages: repair, rebuild and replacement

Paul Industries repairs, rebuilds, retubes and replaces boilers for Missouri owners, supplies replacement boilers, burners and parts on a supply-only basis, and takes design-build and complete installation scopes for boiler plant upgrades with permits, controls and piping included. For the wider view of Paul’s process work in the state, see the Missouri page. To plan a repair, send the nameplate data and MO number, the latest inspection report or insurer letter, the fault history and photographs, and request a quote.

Standards referenced: Missouri Boiler and Pressure Vessel Act, RSMo 650.200 to 650.290 · 11 CSR 40-2, Boiler and Pressure Vessel Safety Rules · ASME Boiler and Pressure Vessel Code, 2019 edition as adopted · National Board Inspection Code, 2019 edition as adopted · ASME B31.1 boiler external piping · ASME CSD-1 · NFPA 85 · NFPA 54 · RSMo 290.230 prevailing wage

Frequently asked questions

Which firm takes boiler repair, St. Louis, MO hospitals and breweries included?

Paul Industries repairs boilers for hospitals, universities, breweries, chemical and life sciences plants and office buildings across St. Louis, St. Louis County, St. Charles County and Jefferson County. Planned repairs move to the months between April and October, and winter work is staged one boiler at a time once the remaining units are confirmed able to carry the load. Paul prepares the boiler for the inspector, makes the repair and handles the records the certificate needs.

Who provides boiler repair in Kansas City, St. Joseph and the Northland?

Paul Industries repairs process and heating boilers in Kansas City, North Kansas City, Liberty, the rest of the Northland and St. Joseph, at animal health, pet food, food processing and automotive plants as well as campuses and government buildings. Those plants usually run production steam all year, so repairs follow the production calendar and the quality unit’s schedule. Boilers at sites with buildings in both states keep their Missouri certificates under the Missouri act.

Who repairs boilers in Springfield, Joplin, Columbia and Cape Girardeau?

Paul Industries repairs boilers in Springfield, Joplin, Columbia, Jefferson City, Cape Girardeau and the rest of central and southern Missouri, at food plants, manufacturers, hospitals, universities and state buildings. Food plants there use steam for cooking and washdown, campuses for heating and hot water, and state buildings bring Missouri’s public works wage rules into replacement projects. Each repair is scheduled around the boiler’s biennial or annual certificate inspection where possible.

How do the Missouri state boiler inspection requirements differ when a boiler carries insurance?

The intervals are the same, annual for power boilers and biennial for heating boilers, but the inspector differs. A boiler under an insurance policy is inspected by the insurer’s commissioned special inspector, who files the report with the chief inspector within 30 days, and the owner pays only the certificate fee. Other boilers are inspected by the state’s chief or deputy inspectors, and the owner pays the inspection fee as well.

What is a Missouri boiler and pressure vessel inspection certificate, and where is it kept?

The inspection certificate is the document the chief inspector issues after a satisfactory certificate inspection and payment of fees. Section 650.265 requires it to show the inspection date and the maximum pressure the boiler may operate at. Rule 11 CSR 40-2.022 makes the owner or user responsible for posting a valid certificate at the boiler’s location, and the certificate expires when the boiler is moved or reinstalled.

Does a Missouri city or county ordinance replace the state boiler program?

Section 650.290 states that the state act does not apply in cities or charter counties that regulate boilers or pressure vessels by ordinance. In those places the city or county program sets the inspection, permit and repair notice requirements. Paul Industries confirms which program holds the boiler’s records before planning a repair, so the right inspector sees the work and the right certificate is renewed.

Who must be told, and how fast, after a Missouri boiler accident?

Rule 11 CSR 40-2.022 requires the owner or user to notify the chief inspector promptly with a detailed report of the accident, and to give notice immediately when an injury, fatality or explosion is involved. The inspector then decides what examination the boiler needs before repair. Paul Industries leaves the damaged area as found until the inspector releases it, then plans the repair and the pressure test with the inspector’s findings in hand.

Which edition of the ASME Code applies to a Missouri boiler repair in 2026?

Rule 11 CSR 40-2.015 incorporates the 2019 ASME Boiler and Pressure Vessel Code and the 2019 National Board Inspection Code, with NBIC Parts 1 and 3 mandatory. Repairs are made to the NBIC and to the rules of the code the boiler was built to. A boiler being rerated to a later ASME edition follows section 650.225, which allows a higher maximum allowable pressure only when the rerating meets that later edition’s rules.

Can a safety valve on a Missouri boiler be repaired at the plant?

Rule 11 CSR 40-2.065 requires code safety and safety relief valves to be repaired by an organization holding a National Board VR Certificate of Authorization whose scope covers that type of valve. The usual practice is to replace the valve with a new one of the same set pressure and capacity, then send the removed valve for VR repair as a spare. No one may alter a relief device to hold a pressure above the one on the certificate.

Does replacing a burner control on an old Missouri boiler trigger an upgrade?

Rule 11 CSR 40-2.030 states that existing installations are exempt from the newer control rules, except that any modification or replacement of controls after January 1, 2004 meets the requirements for new installations. A replaced flame safeguard or burner management system on a boiler under 12,500,000 Btu per hour is therefore brought to ASME CSD-1, and on larger boilers to NFPA 85. Paul Industries prices those upgrades with the repair.

How long does a Missouri boiler certificate stay valid when the inspection is late?

Section 650.260 sets the certificate cycles and allows a grace period of two months between certificate inspections, and the Division of Fire Safety rule gives the inspector 30 calendar days past expiry to perform the inspection. A boiler should never be run on an expired certificate: operating without a valid certificate is a class A misdemeanor under section 650.270, with each day a separate offense.

What happens to a Missouri boiler that is taken out of service or scrapped?

Rule 11 CSR 40-2.022 requires the state tag on an inactivated or scrapped boiler to be bent in half and left on the boiler, and the inspector submits a report showing the new status. A boiler returned to service later needs a certificate inspection first. Paul Industries isolates, drains and lays up boilers taken out of service so they can be inspected and restarted without a fresh repair.

Do agricultural and grain boilers in Missouri need state inspection?

Section 650.230 exempts boilers and pressure vessels located on farms and used solely for agricultural purposes. Boilers at grain processors, feed mills, ethanol plants, creameries and other commercial plants are outside that exemption and carry state certificates like any other plant boiler, so their welded repairs go through the inspector and the National Board R program.

How is a pressure test handled after a Missouri boiler repair?

The NBIC sets the test after a welded repair, and the inspector decides whether a hydrostatic test or another method applies. Rule 11 CSR 40-2.022 states that an inspector-requested pressure test does not exceed the maximum allowable working pressure unless the owner and inspector accept a higher value. Paul Industries schedules the test when the inspector can witness or accept it, and records the pressure, hold time and result in the repair package.

Is boiler water treatment part of a Missouri boiler repair?

Water chemistry is written into Missouri’s rule for very high capacity boilers: a single power boiler over 400,000 pounds per hour qualifies for a two-year internal interval only with water analysis documented at least weekly while running. For any boiler, scale, oxygen pitting and caustic attack found at the repair point to the water treatment program. Paul Industries reviews feedwater, condensate return and blowdown with the repair so the same tubes do not fail again.

Does a boiler replacement at a Missouri school or state building carry prevailing wage?

Section 290.230 requires prevailing wages on public works construction, exclusive of maintenance work, and the Division of Labor Standards publishes rates by county in an annual wage order by July 1. The division treats public works projects of $75,000 or less as outside the law. A boiler replacement at a school or state building usually counts as construction, so Paul Industries prices it with the current wage order.

What clearances does a replacement boiler need in a Missouri boiler room?

For boilers installed or reinstalled on or after January 1, 2010, rule 11 CSR 40-2.030 requires at least 36 inches on each side, 48 inches between boilers in a battery, 36 inches at the front and rear from walls, room to pull and replace tubes, and 84 inches above a top manhole. Manufacturer clearances may be used with the chief inspector’s approval. Paul Industries checks the room against those figures before a replacement is quoted.

Have a Missouri boiler with an inspector's finding or a repeat trip?

Send the nameplate data and MO number, the latest inspection report or insurer letter, the fault history and photographs. Call 201-450-8280 or request a quote.