Paul Industries provides boiler repair in Hawaii for hospitals, hotels and resorts, food and beverage plants, laundries, the Kapolei refinery district and public buildings on Oahu, Maui, Kauai and Hawaii Island, restoring firetube, watertube and cast iron boilers to the ASME code and making pressure-part repairs under the National Board Inspection Code. Each repair is planned around the permit to operate that the Hawaii Boiler and Elevator Inspection Branch issues, so the boiler returns to service with its paperwork complete. Replacement boilers, supplied alone or installed complete, sit inside the same scope.

Request a quote or call 201-450-8280

Headquarters 256 Shore Drive, Kilmarnock, Virginia
Current boiler rules HAR Title 12, Part 10, effective November 1, 2024
Codes adopted ASME BPVC 2021, NBIC 2021, ASME CSD-1-2021
Repair report National Board R form to HIOSH within 30 days (HAR 12-220-8.1)
Unattended power boilers Low-water fuel cutoff tested every 12 operating hours (HAR 12-222.1-10)
Reviewed November 2026

What does boiler repair in Hawaii involve under the 2024 rules?

Boiler repair in Hawaii involves the mechanical work on the boiler plus a permit trail that the state rules spell out step by step: an application before a pressure-part repair starts, a National Board report after it, and an inspection before the permit to operate is renewed. The rules behind that trail are Title 12, Subtitle 8, Part 10 of the Hawaii Administrative Rules, issued under chapter 397 of the Hawaii Revised Statutes. The Governor approved the latest update on September 8, 2024, and it took effect on November 1, 2024, bringing the 2021 editions of the ASME Boiler and Pressure Vessel Code and the National Board Inspection Code into the text along with higher fees.

The repair itself covers the familiar list: leaking or thinned tubes, cracked tube sheets and ligaments, failed refractory and door seals, burners that will not hold a stable flame, flame safeguards and programmers, low-water cutoffs and feedwater controls, relief valves, blowdown and feed piping, and condensate return. On the islands, salt air adds corroded casings, stacks, breechings and burner linkages to that list. The general methods for each of those repairs sit on the boiler repair service page; this page covers what Hawaii’s rules and conditions add.

Which codes does the Hawaii boiler code adopt by reference?

The Hawaii boiler code adopts eight national documents by reference in HAR 12-220-1.1, and they apply to every pressure retaining item in Part 10 unless a later chapter modifies them. A repair crew reads them as a set: the construction code tells you what the boiler was, the inspection code tells you how to put it back, and the controls and combustion codes tell you how it must shut itself down.

Codes adopted by HAR 12-220-1.1 and where each one shows up in a Hawaii boiler repair
Adopted documentEdition in the ruleWhere it governs a repair
ASME Boiler and Pressure Vessel Code2021Original design and materials, replacement parts, weld procedure and welder qualification under Section IX, and Section VI care of heating boilers
National Board Inspection Code2021Part 2 in-service inspection and Part 3 repairs and alterations, including the R forms filed afterward
ASME CSD-12021Controls and safety devices on automatically fired boilers, and the Part CM maintenance and testing schedule
ASME B31.12020Boiler external piping: feedwater, steam stop, blowoff and drain lines up to the code break
NFPA 852019Burner management, purge and fuel train safety on larger and multiple-burner units
NFPA 702017Wiring of burners, controls and electric boilers
ASME PVHO 1 and PVHO 22016Pressure vessels for human occupancy, such as hyperbaric chambers that share a boiler plant

The practical result is that a Hawaii boiler repaired today is judged against code editions newer than the ones many island boilers were built to. Original construction still stands on its own data report, but replacement parts, weld procedures and control upgrades follow the editions in the rule. Paul Industries plans each repair against those editions and records the edition used on every report.

What paperwork does a pressure-part repair need before work starts?

A pressure-part repair on a Hawaii boiler needs an application to the department before the work starts, under HAR 12-220-8.1, and the contents depend on whether the job is a routine repair, a repair or an alteration. The application names the National Board R certificate of authorization number and its expiration date, the authorized inspection agency of record and the commissioned repair inspector, and it arrives with the permit and inspection fees for each item.

Hawaii boiler repair applications by category under HAR 12-220-8.1 and the NBIC
CategoryTypical boiler examplesDocuments sent with the applicationAfter the work
Routine repairSeal welding a tube end, a small handhole repair, as the NBIC defines routine repairsManufacturer’s data report and partial data reports, description of the repair, drawings or photos, material specifications, the written routine repair procedureExecuted R form to the department within 30 days; kept on file, and the inspecting agency may review it
RepairTube replacement or retubing, tube sheet or furnace weld repair, nozzle replacementAll of the above plus design calculations where availableR form to the department within 30 days and registered with the National Board; records kept five years
AlterationRerating to a higher pressure or temperature, changing the heating surface, adding a nozzle that changes the designAll of the above plus design calculations and, where it applies, the new maximum allowable working pressure and temperatureR form to the department within 30 days, registered with the National Board, and a revised permit to operate

Under the rule’s definition, an alteration includes changes that leave the metal untouched: raising the maximum allowable working pressure, raising the design temperature or lowering the minimum temperature all count. Owners sometimes ask for a higher setting to carry a new load, and that request starts the alteration path, with calculations, before any relief valve is reset. Paul Industries sorts each job into the right category at the start, so the application matches the work and the inspector sees what was promised.

The weld map, examination records and written procedure are kept for five years under the rule, and the inspector who handles in-service inspection of the boiler has access to them. Paul Industries hands a copy of the complete repair file to the owner as well, because the next permit renewal inspection will ask about it.

How often is a boiler inspected in Hawaii, and can the interval be stretched?

How often is a boiler inspected in Hawaii depends on its type: power boilers get an annual internal inspection for permit renewal with an external inspection about six months later, while hot water heating and supply boilers get an external inspection every two years under HAR 12-220-16. Steam heating boilers fall between those two, with the interval set by heating surface, burner input and whether the boiler has a manway.

The rule also gives power boiler owners a way to stretch the internal interval, and it ties that option directly to water chemistry. Under subsection (i), a power boiler with continuous internal water treatment, supervised by a qualified engineer or chemist with at least five years of boiler water experience, one of them on the boilers in question, can be given permit inspections at intervals of not more than three years, with external inspections about every six months in between. The owner keeps a record of boiler water samples taken at intervals of no more than 24 hours of operation, plus every outage and its cause, and applies in writing with the water analysis standards achieved over the previous twelve months.

Repairs and water treatment feed each other on that path. A boiler that keeps needing tube work is a poor candidate for a stretched interval, and a clean internal is strong evidence for one. When Paul Industries repairs a power boiler, the report records the condition of the waterside, the deposits found and the corrosion pattern, which is the evidence the department weighs when an extension is requested. Plants that want a broader program can pair the repair with boiler water treatment from the same contract.

What does a boiler inspection consist of on a Hawaii power boiler?

What does a boiler inspection consist of on a Hawaii power boiler: an internal examination of the drums, tubes, furnace and headers, an external examination of the boiler and its appurtenances, and operational tests of the controls and safety devices, which the owner or a designee performs while the inspector watches. HAR 12-222.1-4 makes preparation the owner’s job, and the preparation list is longer than many plants expect.

  • Drain the water and wash the boiler thoroughly.
  • Remove manhole and handhole plates, washout plugs and the inspection plugs in the water column connections, and in internally fired boilers the grates.
  • Cool and clean the furnace and combustion chambers.
  • Remove brickwork or insulation where the inspector needs to see headers, furnace, supports and other parts.
  • Stop steam or hot water from leaking back by disconnecting a pipe or valve, or by a method the inspector approves.
  • Close, tag and padlock the nonreturn, steam stop, blowoff and feed valves before anyone opens a manhole on a boiler that shares a header, and open the drains between valves.

The inspector can also call for a pressure gauge test, a hydrostatic test or anything else needed for continued safety, and the owner must have confined space entry and lockout procedures in place before the boiler is entered. Paul Industries prepares boilers for the Hawaii boiler inspection as part of the outage: the waterside is opened and washed, refractory is cut back where needed, valves are locked out to the inspector’s approval, and any defects found are quoted and repaired before the boiler is closed. One outage then covers both the inspection and the work it turns up.

Unattended power boilers: the Hawaii log and low-water rules

Unattended power boilers in Hawaii must meet the conditions in HAR 12-222.1-10, which apply whenever a power boiler, waste heat boiler or high-temperature water boiler is left longer than it takes the water level to fall from normal to the lowest permissible level with the feedwater shut off at full firing. Many hospital, hotel and food plant boilers run under those conditions overnight, so the controls the rule names are often where repair work concentrates.

HAR 12-222.1-10 conditions for unattended power boilers and the repair work each one drives
Condition in the ruleInterval or detailRepair and test work it drives
Daily operating log at the boilerEntries updated daily, no single entry longer than 12 hours; kept for at least six monthsLog sheets matched to the boiler’s controls after any control change
Low-water alarmStrobe or flashing light visible from the farthest point the attendant works; audible alarms heard above ambient noiseAlarm wiring, light placement and sound level checks after a control upgrade
Two low-water safety devicesSeparate water connections; fuel shut off at the lowest permissible level; manual reset unless the burner has a full safety pilotRebuilding or replacing probe and float cutoffs, re-piping their connections, verifying manual reset
Attendant roundsBoiler, auxiliaries and water level checked at intervals not exceeding 60 minutesGauge glass and water column repairs so rounds read true
Fuel cutoff testAt the start of each daily period and at intervals not exceeding 12 operating hours, with records kept six monthsSlow-drain and evaporation tests, blowdown valve repair, test records for the inspector
Emergency disconnectAt the boiler room entrance, or beside an outdoor boiler, with a sign directing its useDisconnect relocation and signage when a boiler room is rebuilt

The competent attendant described in the rule must be able to explain every control and safety device, know each way of feeding water to the boiler, and shut the boiler down safely, measured against ASME Section VII. Paul Industries walks plant staff through every control it repairs or replaces, so the attendant’s knowledge keeps pace with the hardware.

Relief valves, controls and the Test Only nameplate

Relief valves on Hawaii boilers follow HAR 12-220-10, which forbids repairing or removing a pressure relief device while it is under pressure and requires every valve removed during an outage to be back in place and working before the boiler returns to service. Safety valve repairs are made under the National Board VR program, and a valve that has been tested and reset to its original set pressure without other repair receives a Test Only nameplate.

The same section bars altering a safety or relief valve to hold a pressure above the one on the permit to operate, which is why an alteration comes before any rerating. Paul Industries removes, tests and replaces relief valves inside the outage window, keeps the set pressure and capacity matched to the nameplate and permit, and documents each valve by serial number. Low-water cutoffs, flame safeguards, gas trains and limit controls are tested to ASME CSD-1 and returned with a test sheet, and heating boilers are serviced to the Section VI and CSD-1 Part CM schedules that HAR 12-223.1-14 names.

Do you need a permit for a boiler replacement in Hawaii?

Do you need a permit for a boiler replacement in Hawaii: yes for any boiler inside the rules, because HAR 12-220-15 bars anyone from installing, constructing, reconstructing or relocating a pressure retaining item without an installation permit from the department. The plans and specifications go in before work starts, along with the manufacturer’s data report, the National Board number, a floor plan with clearances and a piping and instrumentation diagram.

The rule issues installation permits only to a person holding a contractor’s license from the Contractors License Board of the Department of Commerce and Consumer Affairs for installing or repairing pressure retaining items. A complete application is deemed approved if the department has not acted on it within thirty calendar days, and plans must be resubmitted when installation has not started within three years of approval. Once the new boiler passes its acceptance inspection, the state of Hawaii boiler permit to operate shows the equipment type, the maximum allowable working pressure and the National Board number, and it is posted where the boiler sits.

Some boilers fall outside these steps. Directly fired hot water supply boilers, hot water heating boilers and potable water heaters are exempt when none of four limits is exceeded: 200,000 Btu per hour of input, 210 degrees Fahrenheit, 120 gallons of water capacity and 160 psi of operating pressure, though hot water supply boilers still need a properly sized Section IV relief valve. Items under federal jurisdiction and units serving a private residence that the public cannot reach are also outside the state inspections.

A used boiler brought in from elsewhere must arrive with in-service inspection reports covering at least its last five years and copies of any repair or alteration reports, under HAR 12-220-5, and its fittings must meet the requirements for a new installation. Paul Industries prepares the state of Hawaii boiler permit application, the drawings and the data package for each replacement it supplies, and coordinates the acceptance inspection with the validation and commissioning in Hawaii scope when the boiler serves a regulated process.

Boiler repair on each island

Boiler repair on each island follows the same state rules, but the boilers, owners and utility arrangements differ from Oahu to Kauai. Hawaiian Electric serves Oahu, Maui County and Hawaii Island, and Kauai Island Utility Cooperative serves Kauai, so the electrical side of a burner or electric boiler repair is coordinated with whichever utility serves the site.

On Oahu, Honolulu hospitals, hotels and laundries run steam and hot water boilers for sterilizers, kitchens and linen, and Kapolei and Campbell Industrial Park add the refinery district and the plants around it; the EIA lists Par Hawaii Refining at Kapolei with 93,500 barrels per calendar day of distillation capacity on January 1, 2026. Boilers inside Pearl Harbor and other federal installations are under federal jurisdiction rather than the state permit system, and their repairs follow the owner’s own inspection program and the NBIC. On Maui, the Kahului industrial area and resort central plants carry most of the island’s boilers; on Hawaii Island, hospitals, food processors and resorts around Hilo and Kona; and on Kauai, the Lihue area plants and hotels.

Every repair Paul Industries plans in Hawaii starts with parts staged ahead of the outage. Tubes, gaskets, refractory, relief valves and control components are identified from the nameplate data and last inspection report, then held for the job, so the boiler is opened once and closed once.

What happens after a boiler accident in Hawaii?

After a boiler accident in Hawaii, the owner, user or maintenance company reports it to the HIOSH division, and the deadlines are short: within eight hours when a death occurs and within twenty-four hours when someone is admitted to a hospital, under HAR 12-220-27. The damaged boiler and its parts stay where they are until the department gives permission, except to save a life or limit further damage.

The rule’s definition of an accident excludes routine events such as tube leaks, general leakage, corrosion and erosion, which are treated as maintenance and repair. Violations of chapter 397 or the rules carry civil penalties of up to $10,000 each, and each day a violation continues counts separately outside an abatement period. When the department orders a boiler made safe, the owner can be granted up to ninety days to comply. Paul Industries works to the schedule in the order, documents each corrected item for the reinspection and keeps the owner’s file ready for the inspector’s return.

How often do boilers need to be replaced in Hawaii plants?

How often do boilers need to be replaced has no fixed answer in the Hawaii rules; a boiler stays in service as long as it passes its permit renewal inspections and repairs keep it safe at its permitted pressure. Replacement usually comes when repairs stop making economic sense: repeated tube failures, a cracked furnace or tube sheet, a pressure vessel thinned below its required thickness, or controls so old that parts are hard to source.

Two Hawaii factors weigh on that decision. The first is the installation permit: a new boiler means a new application, acceptance inspection and permit to operate, while a repair keeps the existing permit in force with an R form on file. The second is that a replacement is a chance to correct what island conditions have done to the old installation, such as corroded breechings, stacks and burner housings, and to choose stainless or coated components where salt air reaches the boiler room. Paul Industries prices repair and replacement side by side, with the permit steps and outage length for each, so the owner compares complete paths rather than equipment prices alone.

What does boiler repair in Hawaii cost?

The cost of boiler repair in Hawaii depends on the boiler type and size, the repair category under the NBIC, the parts and materials involved, how much of the work must happen inside an operating plant, and the state permit and inspection fees that apply to each item. A burner or control repair with no pressure-part welding costs far less than a retube, which needs an application, a repair inspector, examination and a National Board report.

Public work adds a line of its own: state and county construction projects over $2,000 pay prevailing wages under chapter 104 of the Hawaii Revised Statutes and file payroll records with the contracting agency. For a budget range, send the boiler nameplate and National Board number, the current permit to operate, the last inspection report and any discrepancy letter, photographs of the fireside and waterside, the burner and control make, and the outage window. Paul Industries returns a range from comparable scope, then a firm price once the boiler is opened and the repair category is confirmed.

Who repairs boilers in Hawaii?

Paul Industries repairs boilers in Hawaii for hospitals, hotels and resorts, food and beverage plants, laundries, refinery and terminal operators, schools and public buildings on Oahu, Maui, Kauai and Hawaii Island. Paul Industries is headquartered at 256 Shore Drive, Kilmarnock, Virginia, and takes work across Hawaii, in all 50 states and at plants outside the United States through its international projects; the process equipment contractor in Hawaii page describes the full island scope.

A boiler job often touches the systems around it, and Paul Industries carries those under the same contract: welded pressure-part work described on the industrial welding services in Hawaii page, steam and condensate lines covered by process piping in Hawaii, deaerators and receivers through pressure vessel fabrication in Hawaii, and central plant cooling through chiller repair in Hawaii. Owners comparing state requirements can read the California boiler repair page for the Cal/OSHA permit cycle, and the boiler repair in Virginia, the headquarters state page for the rules at home.

Boiler repair from Paul Industries for Hawaii owners

Paul Industries repairs, retubes, rebuilds and replaces boilers in Hawaii, tests and repairs their controls, burners and relief valves, prepares boilers for permit renewal inspections, and assembles the applications, R forms and test records the Boiler and Elevator Inspection Branch expects. Supply-only boilers and parts, design-build replacements and complete installations are all available, and each job ends with a repair file the owner keeps. To start, request a quote or call 201-450-8280 with the boiler’s nameplate and latest inspection report.

Standards referenced: Hawaii Revised Statutes chapter 397 (Boiler and Elevator Safety Law) · Hawaii Administrative Rules Title 12, Subtitle 8, Part 10, chapters 12-220, 12-222.1 and 12-223.1 (as amended September 8, 2024, effective November 1, 2024) · ASME Boiler and Pressure Vessel Code, 2021 edition, Sections I, IV, VI and IX · National Board Inspection Code, 2021 edition, Parts 2 and 3 · ASME CSD-1-2021 · ASME B31.1-2020 · NFPA 85, 2019 edition · Hawaii Revised Statutes chapter 104 (wages on public works)

Frequently asked questions

Who repairs boilers at Honolulu hospitals and Kapolei plants?

Paul Industries repairs boilers at Honolulu hospitals, hotels and laundries and at Kapolei and Campbell Industrial Park plants, including tube and refractory work, burner and flame safeguard repairs, low-water cutoff and relief valve work, and welded pressure-part repairs under NBIC Part 3. Hospital boilers are worked one at a time so heating and sterilizer steam stay available, and each repair is filed with the department as the Hawaii rules require.

Which firm handles boiler repair in Hilo, Kona, Kahului and Lihue?

Paul Industries handles boiler repair in Hilo and Kona on Hawaii Island, Kahului on Maui and Lihue on Kauai for hospitals, resorts, food processors and public buildings. The work follows the same state rules as on Oahu, and parts, gaskets, refractory and relief valves are staged before each outage from the boiler’s nameplate data and last inspection report, so the boiler is opened and closed once.

Who is the Hawaii boiler inspector for a boiler covered by insurance?

A boiler covered by insurance is usually inspected by a special inspector employed by the insurance company and authorized by the department under HAR 12-220-16, while uninsured boilers are inspected by the department’s own inspectors. Either way, the Hawaii boiler inspector’s report is what the permit to operate rests on. Paul Industries prepares the boiler for that inspector and repairs whatever the report lists.

What does the Hawaii Boiler and Elevator Inspection Branch do?

The Hawaii Boiler and Elevator Inspection Branch, part of HIOSH in the Department of Labor and Industrial Relations, administers the Boiler and Elevator Safety Law. It writes standards, inspects, investigates, reviews and approves plans for new installations, repairs and modifications, and issues permits to operate boilers, pressure vessels and pressure systems found safe. Paul Industries assembles the documents the Branch asks for with each repair or installation.

When did the current Hawaii boiler rules take effect?

The current Hawaii boiler rules, Title 12, Subtitle 8, Part 10 of the Hawaii Administrative Rules, were approved by the Governor on September 8, 2024 and took effect on November 1, 2024. The update adopted the 2021 editions of the ASME Boiler and Pressure Vessel Code and the National Board Inspection Code, added more detailed procedures and raised fees. Paul Industries plans every repair against those editions.

Can a Hawaii boiler keep running while its permit renewal is late?

A Hawaii boiler without a valid permit to operate may run only as needed to install, repair or test it, under HAR 12-220-15. An owner can ask the chief boiler inspector in writing to extend a valid permit for cause, but the rule says the absence of a special inspector is not a valid reason. Paul Industries books repairs and inspection preparation ahead of the expiration date to keep the permit current.

How is a boiler rerating handled in Hawaii?

A boiler rerating in Hawaii is an alteration under the rule’s definition, even when no metal changes, because raising the maximum allowable working pressure or design temperature counts as one. The application carries design calculations, the data reports and the new pressure and temperature, and the work ends with a registered R form and a revised permit to operate. Paul Industries prepares the calculations and resets the relief valves only after approval.

Does a Hawaii steam heating boiler need an annual internal inspection?

A Hawaii steam heating boiler needs an annual internal inspection when it has a manway, more than 400,000 Btu of input or more than 100 square feet of heating surface; smaller steam boilers between 20 and 100 square feet are inspected externally every two years and internally at least every four. Paul Industries times tube, gasket and control repairs to those inspections so the boiler opens once.

Is a large water heater in a Hawaii hotel covered by the boiler rules?

A water heater in a Hawaii hotel is covered when it exceeds any one of four limits: 200,000 Btu per hour of input, 210 degrees Fahrenheit, 120 gallons of capacity or 160 psi of operating pressure. Below all four, a directly fired unit is exempt from the permit to operate. Covered units receive an external inspection every two years. Paul Industries repairs and replaces both classes and keeps the covered ones on their permit cycle.

Who repairs the safety valves on a Hawaii boiler?

Safety valve repairs on a Hawaii boiler are made under the National Board VR program, as HAR 12-220-10 requires, and a valve that is only tested and reset to its original set pressure receives a Test Only nameplate. Paul Industries removes the valves during the outage, returns them tested or replaced with matching set pressure and capacity, and reinstalls them before the boiler goes back into service.

What records does a Hawaii plant keep after a welded boiler repair?

After a welded boiler repair, a Hawaii plant should hold the executed National Board R form, which reaches the department within thirty days, plus the drawings or photos, calculations, nondestructive examination records and the written repair procedure. The rule keeps those records for five years and lets the in-service inspector review them. Paul Industries hands the owner a complete copy as one repair file.

How fast must a boiler accident be reported in Hawaii?

A boiler accident that causes a death must be reported to HIOSH by phone or email within eight hours, and one that leads to inpatient hospitalization within twenty-four hours, under HAR 12-220-27. Every accident also needs a detailed written report. The boiler stays untouched until the department allows it, except to save life or limit damage. Paul Industries then repairs the boiler to the department’s findings.

What does a variance from the Hawaii boiler rules involve?

A variance from the Hawaii boiler rules is a written request to the director showing that an alternative method gives a substantially equivalent level of safety, with drawings and supporting data. Before granting one, the director posts a notice online and allows thirty calendar days for objections. Paul Industries prepares the technical case when a repair or replacement needs an alternative to a specific requirement.

Can a used boiler from the mainland be installed in Hawaii?

A used boiler can be installed in Hawaii when the owner provides in-service inspection reports for at least its last five years and copies of any repair or alteration reports, under HAR 12-220-5, and its fittings meet the rules for new installations. It also needs an installation permit and an acceptance inspection. Paul Industries reviews the history, repairs what is needed and installs it to the current rules.

What is checked during an operational test on a Hawaii boiler?

An operational test on a Hawaii boiler exercises the controls and safety devices while the inspector watches: low-water cutoffs, flame failure, high limit and pressure controls, and the alarm. On power boilers this happens at the initial acceptance inspection and again about six months after each annual internal. Paul Industries runs those tests with plant staff and records the results for the inspection file.

Does Paul Industries replace boilers at Hawaii food and beverage plants?

Paul Industries replaces boilers at Hawaii food and beverage plants, including the application for the installation permit, removal of the old unit, installation of the new boiler with its external piping, controls and relief valves, and the acceptance inspection that leads to the permit to operate. Steam for cooking, washdown and CIP is planned so production can continue through the changeover.

What should a Hawaii facility send to price a boiler repair?

Send the boiler nameplate and National Board number, the current permit to operate, the latest inspection report and any discrepancy letter, photographs of the fireside and waterside, recent water treatment records, the burner and control make, the island and site, and the outage window. Paul Industries returns a budget range from comparable work, then a firm price once the repair category is set. Call 201-450-8280 or request a quote.

Boiler written up or due for its Hawaii permit inspection?

Send the nameplate, the permit to operate, the last inspection report and the outage window you can give. Call 201-450-8280 or request a quote.