Paul Industries designs, installs, services and retrofits data center cooling in Virginia, from chilled-water plants and water-side economizers to CRAH galleries and fan walls, working from its headquarters at 256 Shore Drive in Kilmarnock. Virginia cooling work is shaped by three things that a generic design misses: a humid mixed climate that rations free cooling, a power grid where every megawatt spent on fans and compressors is a megawatt withheld from servers, and county water systems now asked to account for every gallon a campus evaporates.
Request a quote or call 201-450-8280
What makes data center cooling in Virginia different?
Data center cooling in Virginia has to work inside a mixed-humid climate, a constrained transmission grid and growing scrutiny of water use, all at once. Most of the Commonwealth, including Loudoun, Prince William and Henrico counties, sits in climate zone 4A under the 2021 IECC map, while Norfolk, Virginia Beach and several other Hampton Roads cities fall in the warmer 3A zone. Summers are long and wet; winters are cold enough to freeze an unprotected dry cooler. A plant that suits Phoenix or Dublin will either waste energy here or leave economizer hours unused.
Scale amplifies every decision. The Joint Legislative Audit and Review Commission reported in December 2024 that Virginia held more than 63 million square feet of data center space on about 7,200 acres, drawing roughly 5,050 MW. A few tenths of a point of mechanical efficiency across that much load is a power plant’s worth of difference, which is why owners in Ashburn, Manassas and Sterling now ask cooling contractors for annual energy models, not just peak tonnage.
Paul Industries is a Virginia company, so these constraints are the ones its own home market is built around. The Virginia overview describes the wider process and pharmaceutical work Paul delivers across the state; this page stays with the cooling plant.
Northern Virginia weather, hour by hour
For data center cooling, Northern Virginia weather gives a plant roughly 3,600 hours a year below 50°F dry bulb and about 1,670 hours above a 67°F wet bulb, based on the long-term engineering weather record for Washington Dulles International Airport. Those two numbers frame the whole design: the first is the economizer opportunity, the second is the humid stretch when compressors and towers carry the load.
| Design condition | Value | What it sizes |
|---|---|---|
| 0.4% cooling dry bulb | 93°F with 76°F mean coincident wet bulb | Air-cooled chillers, dry coolers, condenser fans |
| 0.4% evaporation wet bulb | 78°F with 89°F mean coincident dry bulb | Cooling towers, evaporative fluid coolers, adiabatic pads |
| 1% dehumidification | 126 grains per pound, about a 73°F dew point | Makeup air units, humidity control for the white space |
| 99.6% heating dry bulb | 9°F, with a median extreme low near minus 1°F | Glycol concentration, heat tracing, freeze protection |
| Cooling degree days (base 65°F) | 1,250 a year, peaking at 348 in July | Seasonal energy models |
Many owners now size heat rejection above the 0.4% values, often to the median extreme or beyond, because a hall that trips on the hottest afternoon of the decade has failed regardless of its average efficiency. The record above is the published engineering summary for the Dulles station; a design team should confirm current-edition ASHRAE values for the final basis of design, and Paul Industries builds the plant to whichever extreme the owner selects.
| Dry-bulb band | Hours per average year | Typical cooling mode with 65°F chilled water |
|---|---|---|
| Below 50°F | About 3,590 | Full water-side economizer; chillers off or idling |
| 50°F to 59°F | About 1,370 | Full or partial economizer, depending on coincident wet bulb (52°F or lower on average) |
| 60°F to 69°F | About 1,600 | Partial economizer with chillers trimming |
| 70°F to 79°F | About 1,410 | Mechanical cooling; towers carry the condenser load |
| 80°F and above | About 790 | Full mechanical cooling at or near design |
Raising chilled water temperature is the single most effective way to move hours up this table into economizer territory. A plant designed around 45°F supply water sees only the coldest winter nights as free; one designed around 65°F, which modern servers tolerate inside the ASHRAE recommended envelope, spends most of the cool season with chillers idle.
Air-side or water-side economizers in a humid climate?
Water-side economizers are the usual choice for large Virginia halls because outdoor air in Northern Virginia is too wet for direct use through much of the warm season. The ASHRAE recommended envelope for IT equipment tops out at an 80.6°F inlet and a 59°F dew point, and the Dulles record shows a 1% dew point near 73°F. Bringing that air into the white space means dehumidifying it first, which erases most of the saving.
For data center cooling, Loudoun County halls built in the last decade lean on plate heat exchangers between the condenser water and chilled water loops. When the wet bulb drops far enough for the towers to make water a few degrees colder than the chilled water return, the exchanger carries part or all of the load and the chillers unload. Integrated economizers, which run the exchanger and the chillers in series, capture the shoulder hours in spring and autumn that an all-or-nothing changeover would waste.
Air-side economizers still have a place in Virginia: smaller enterprise rooms, edge sites in the Shenandoah Valley and Southwest Virginia, where elevation brings drier and cooler air, and indirect evaporative units that use outdoor air on one side of a heat exchanger without letting it touch the servers. For data center cooling, Ashburn operators running indirect evaporative units still need water for the evaporative stage on humid days, so the water question below applies to them as well.
Controls decide whether any of this works. A changeover sequence that hunts between modes every time a front passes through the Potomac basin will wear valves and trip chillers. Paul Industries programs and tests the transitions with deadbands and minimum run times, and links the sequence to the chilled water system it serves rather than leaving it to a default controller setting.
Virginia data center electricity demand and the cooling share
Virginia data center electricity demand is the constraint that most changes cooling priorities, because utility capacity, not floor space, now limits how much IT load a campus can energize. JLARC found that building enough generation and transmission to meet forecast Virginia data center energy demand will be difficult, and recommended that utilities be allowed to delay new service where the grid cannot support it. A campus with a fixed utility allocation can only add servers by spending less of that allocation on cooling.
The arithmetic is direct. At the 2024 Virginia industrial average of 8.99 cents per kilowatt-hour (EIA), every kilowatt of continuous mechanical load costs about $788 a year. The table below shows what the cooling overhead of a 10 MW IT hall costs at different levels of plant efficiency.
| Mechanical overhead (kW per kW of IT) | Cooling power | Energy per year | Cost per year |
|---|---|---|---|
| 0.35 | 3.5 MW | 30.66 million kWh | About $2,756,000 |
| 0.25 | 2.5 MW | 21.90 million kWh | About $1,969,000 |
| 0.15 | 1.5 MW | 13.14 million kWh | About $1,181,000 |
| 0.10 | 1.0 MW | 8.76 million kWh | About $788,000 |
Actual data center tariffs differ from the statewide industrial average, and real halls rarely run at constant full load, so the figures are a basis for comparison rather than a bill. The point holds at any rate: on Virginia data center power consumption, moving a plant from 0.35 to 0.15 frees 2 MW that can be sold to tenants instead of spent on compressors.
Code now pushes in the same direction. The 2021 Virginia Uniform Statewide Building Code, effective January 18, 2024, carries a Virginia Energy Conservation Code built on the 2021 IECC, which sends data center mechanical systems to the mechanical load component limits of ASHRAE 90.4. New plants and major alterations have to show their cooling efficiency on paper before the building official signs off.
What the Northern Virginia data center disconnect taught cooling designers
The Northern Virginia data center disconnect of July 10, 2024 showed that a cooling plant must ride through a grid disturbance as reliably as the servers do. A fault on a 230 kV transmission line caused about 60 data centers, roughly 1,500 MW of load, to transfer from the grid to their own backup power at the same moment, an event NERC later examined in an incident review on large load loss. The IT load stayed up because UPS systems carried it; the cooling plant has no UPS and has to restart on generators. Northern Virginia data center power arrives through a transmission network that, as that evening showed, can see 1,500 MW vanish in seconds.
Chillers are the weak point in that sequence. A centrifugal machine that loses power coasts down, and depending on its controls it may take several minutes before it is back at full capacity. During that gap the heat keeps coming. Designs that handle it well share a few features:
- Chilled water thermal storage tanks, or simply a large enough loop volume, sized to carry the hall through the chiller restart window.
- Chillers with rapid-restart controls, and pumps and CRAH fans on UPS or on a fast generator step so that stored cold water keeps moving.
- A sequence of operations that restarts chillers in a staged order on generator power instead of all at once, so the generators are not overloaded.
- Economizer valves that fail to a safe position, so a transfer in winter does not strand the plant in a mode it cannot hold.
A Virginia data center power outage, or even a voltage sag that the facility treats as one, is now a design case rather than a rare event. Paul Industries sizes storage, programs restart sequences and proves them during data center commissioning in Virginia, where the transfer test is witnessed with the cooling plant under real heat load.
How much water do Virginia data centers use for cooling?
Virginia data center water use depends almost entirely on the heat rejection method: evaporative towers consume water continuously, while closed loops with dry coolers use very little. By the county’s own figure, Loudoun County data center water usage accounts for about 9% of total potable water use on an average day. JLARC found statewide data center water use sustainable for now, but growing, and recommended that counties be allowed to require water use estimates before approving new sites.
The split is stark. Loudoun County’s own figures put evaporation at 75 to 85% of the water an open cooling system takes in, with the remaining 15 to 25% leaving as blowdown wastewater; closed systems lose between zero and 5%. Water use therefore traces back to a handful of design choices: tower or dry cooler, the number of cycles of concentration the water treatment program can hold, and whether adiabatic assist runs only on the hottest hours or all summer.
Reclaimed water changes the picture in eastern Loudoun. Loudoun Water began building its reclaimed water system in 2010 for early data centers and delivered more than 750 million gallons of reclaimed water to roughly 40 customers in 2025. Northern Virginia data centers water treatment on reclaimed supply is a different program from potable makeup, with more phosphate, ammonia and suspended solids to manage, and the tower metallurgy and cooling tower water treatment have to be chosen for it from the start.
Virginia data center water consumption can be cut sharply without giving up evaporative efficiency entirely. Hybrid plants run dry coolers through the roughly 3,600 hours below 50°F, switch to evaporative assist only when the dry bulb climbs, and keep towers for the humid peak. The data center cooling towers page covers tower selection in detail; for Virginia projects Paul models the hybrid split hour by hour against the Dulles or Richmond record so the owner can state annual water use with confidence in a county application.
Redundancy choices for Virginia cooling plants
Cooling redundancy for a Virginia data center is chosen by deciding which single failure the hall must survive at full load on a design day. Colocation tenants in Northern Virginia often write redundancy into their leases, so the plant topology is part of the commercial product, not only an engineering choice.
| Scheme | Arrangement | Survives | Cost and space impact |
|---|---|---|---|
| N | Just enough chillers, towers and pumps for design load | Nothing at peak; maintenance only in mild weather | Lowest |
| N+1 | One spare unit of each type | Loss of any one chiller, tower cell or pump | Moderate; one extra unit per equipment group |
| N+2 | Two spares per group | One unit failed while another is down for maintenance | Higher; common for large chiller plants |
| 2N | Two complete, separate plants or loops | Loss of an entire plant, header or electrical path | Highest; doubles equipment and much of the piping |
| Distributed redundant | Load spread across several plants, each with spare capacity | Loss of one plant with others absorbing its share | Between N+1 and 2N; complex controls |
Piping is where redundancy schemes are won or lost. A 2N plant that shares one header, or an N+1 plant whose spare chiller cannot be isolated without draining the loop, has a single point of failure the equipment count hides. Paul Industries lays out valving so every chiller, pump and tower cell can be isolated live, and builds ring headers or dual paths where the owner’s tier target calls for them, using the same welded and grooved closed loop cooling practices it applies to process plants.
CRAH galleries, fan walls and containment
CRAH galleries and fan walls move the cooling coils out of the white space and into a service corridor, which suits the large single-story halls common in Prince William and Loudoun counties. A fan wall pushes a large volume of air across a long face of the hall at low velocity, and service staff reach coils, valves and filters without entering the secure server floor.
Containment is what makes warm chilled water possible. With hot aisles fully enclosed and ducted back to the gallery, return air reaches the coils hot, the coil can run a wide temperature difference, and supply air can sit near the upper end of the recommended range without hot spots. Without containment, mixing forces colder supply air, colder water and fewer economizer hours, which in Virginia’s climate is an expensive trade.
Condensation is a Virginia-specific concern in galleries. With outdoor dew points regularly above 70°F in summer, any chilled water pipe, valve body or coil header colder than the surrounding air will sweat if its mechanical insulation has a gap. Paul insulates and vapor-seals every cold surface, including valve bonnets and strainer caps that are often left bare.
Cooling beyond Northern Virginia: Richmond, Southside and Hampton Roads
Data center development in Virginia has begun spreading into new areas such as the Interstate 95 corridor toward Richmond, according to JLARC, and each region changes the cooling design. Henrico and Chesterfield counties share Northern Virginia’s 4A climate zone but typically run a little warmer; for data center cooling, Richmond projects see more cooling degree days and a shorter economizer season than an Ashburn hall, so warm chilled water and integrated economizers matter even more.
Hampton Roads is different again. Transatlantic cables including MAREA, BRUSA and Dunant land at Virginia Beach, which makes a data center Virginia Beach site attractive for network reasons, and the city sits in the warmer 3A zone. Coastal salt air attacks the fins of dry coolers and air-cooled condensers, so coated coils and stainless or coated fasteners belong in the specification, and cooling towers need drift eliminators and basin materials chosen for a marine atmosphere.
Across the Shenandoah Valley and the Roanoke and Lynchburg areas, higher elevations bring cooler nights and more economizer hours, but also colder winters. Dry coolers and outdoor piping there need glycol at concentrations that hold through the region’s extreme lows, which in turn reduces heat transfer and raises pump energy, so the glycol choice is a balance rather than a default; the glycol cooling systems page explains the trade.
Virginia data center locations away from Loudoun also tend to have less established water and sewer capacity for blowdown, which pushes designs toward closed loops and dry heat rejection. Paul Industries matches the plant to the site’s utilities rather than carrying a Loudoun template south.
Sound limits and heat rejection equipment
Sound from cooling equipment has become a permitting issue for Virginia data centers because yard and rooftop heat rejection is the main continuous noise source on many sites. JLARC found that noise has affected neighboring residents in a few cases and recommended that counties be allowed to require sound modeling studies before approving new projects.
Cooling choices drive the sound model. Large-diameter, low-speed fans on towers and dry coolers, variable-speed drives that slow fans through the many mild hours, acoustic screens and careful siting of equipment away from property lines all lower the modeled level. Air-cooled chillers packed on a roof are typically the hardest case. Paul selects heat rejection with the sound study in hand, so the plant that wins the energy model also passes the county’s review.
What does data center cooling cost in Virginia?
Data center cooling cost in Virginia is driven mainly by heat rejection type, redundancy level, chilled water temperature and whether the work is new construction or a retrofit inside an operating hall. Installed cost for a new plant is usually dominated by chillers, towers or dry coolers, pumps and the large-bore piping that ties them together; a retrofit adds phasing, temporary cooling and work around live equipment.
- Heat rejection: towers cost less to buy than equivalent dry coolers but carry water, treatment and blowdown costs for the life of the plant; hybrids cost more up front and less to run.
- Redundancy: each step from N+1 toward 2N adds equipment, piping, valves and controls.
- Supply temperature: warmer water allows smaller chillers and more economizer hours but needs containment and coils selected for it.
- Thermal storage: tanks for ride-through add cost and site area, and remove a real failure mode.
- Energy over the life of the plant: at 8.99 cents per kilowatt-hour, the energy table above often outweighs the first-cost difference between plant options within a few years.
For a budget range, Paul Industries works from the IT load, the redundancy target, the site location and any utility or water limits; a firm price follows once the design basis and drawings are set. Owners comparing a liquid cooling retrofit in Virginia against a plant upgrade can price both routes together, because the facility water side of a liquid cooled row is often the existing chilled water plant.
Who designs and installs data center cooling in Virginia?
Paul Industries designs and installs data center cooling in Virginia, from chilled-water plants and economizer heat exchangers to gallery piping, CRAH connections and thermal storage, and services the plants it builds. Paul is headquartered in Kilmarnock on the Northern Neck and takes cooling work in Northern Virginia, Richmond, Petersburg, Hampton Roads, Charlottesville, the Shenandoah Valley, Roanoke, Lynchburg and Southside, as well as in all 50 states.
Owners choose the route that fits the project:
- Supply only: chillers, pumps, plate heat exchangers, prefabricated pump skids and pipe spools, delivered to the owner’s installer with submittals and test records.
- Design-build: Paul sets the basis of design, models annual energy and water against Virginia weather, produces drawings and builds the plant under one contract.
- Complete installation: Paul installs to the engineer of record’s drawings, from setting equipment through pressure testing, flushing, startup and turnover.
Retrofits and service run alongside new work: chiller replacements, economizer additions to older plants, controls rewrites, and chiller repair in Virginia for plants already in operation. For multi-building campuses where cooling is one package among several, the data center mechanical contractor in Virginia page covers central plant and campus-wide piping delivery.
Paul Industries and Virginia data center cooling
Paul Industries builds data center cooling plants for Virginia’s climate, grid and water rules: warm chilled water and integrated economizers to use the cool hours Northern Virginia offers, storage and restart sequences that hold through a grid event, and heat rejection chosen for water, sound and coastal or mountain sites. The plant stays with Paul from drawing to maintenance: design, fabrication, supply, installation, testing, startup and service, and the national data center cooling systems page covers the full range of methods. To price a new plant, an economizer retrofit or a service agreement, request a quote or call 201-450-8280.
Standards referenced: ASHRAE Thermal Guidelines for Data Processing Environments · ASHRAE 90.4 · 2021 Virginia Uniform Statewide Building Code · Virginia Energy Conservation Code · Virginia Mechanical Code · ASME B31.9 · ASHRAE Handbook Fundamentals climatic design data
Frequently asked questions
How is an Ashburn, Virginia data center cooled through a humid July?
In July an Ashburn, Virginia data center runs mostly on mechanical cooling, with chillers rejecting heat through cooling towers or dry coolers and economizers largely idle. Dulles averages 348 cooling degree days in July alone, and wet bulbs above 67°F are routine. Plants designed for 60 to 65°F chilled water still save energy in July because each chiller works across a smaller lift, and towers can often pick up partial economizer duty overnight when the wet bulb drops.
Why are there so many data centers in Virginia, and how does that shape cooling work?
JLARC credits several factors: access to high-voltage transmission, large flat sites close to customers, and a state sales tax exemption on data center equipment that has been in place since 2010 and is used by about 90% of the industry measured in megawatts. For cooling, the concentration means utility capacity and county review are tight, so efficient plants, documented water use and quiet heat rejection decide which projects move forward.
How much water do Virginia data centers use?
Virginia data center water usage varies widely by design. A campus on evaporative towers can draw large volumes through summer, while one on closed loops and dry coolers uses little beyond fill and occasional makeup. In Loudoun County, data centers account for about 9% of potable water use on an average day, and reclaimed water supplied by Loudoun Water offsets part of the demand. Paul models expected annual use for each plant option so owners can report a defensible figure.
Do Virginia data centers use water when the cooling loop is closed?
A closed chilled water or technology cooling loop holds the same water for years, losing only small amounts to leaks, sampling and maintenance draining; Loudoun County puts closed-system losses at zero to 5%. Water consumption comes from the heat rejection side. If the closed loop rejects heat through a dry cooler, the site uses very little; if it rejects through an evaporative tower or adiabatic pads, that equipment consumes water whenever it runs.
Can a Virginia data center run its cooling towers on reclaimed water?
Reclaimed water is already used for data center cooling in eastern Loudoun, where Loudoun Water has supplied it since 2010. It works, but it changes the treatment program and materials: reclaimed water carries more nutrients, ammonia and suspended solids than potable supply, which raises biofouling and corrosion risk. Paul selects tower fill, basin materials, filtration and chemistry for the actual supply and designs a potable backup connection for interruptions.
What chilled water supply temperature suits a Northern Virginia hall?
Many new Northern Virginia halls run 60 to 70°F supply water, made possible by hot aisle containment and coils selected for a wide temperature difference. At those temperatures the Dulles record offers thousands of economizer hours a year. Older halls at 42 to 45°F can often be raised in steps once airflow is fixed. The right value depends on the IT equipment’s inlet limits, coil selection and how much humidity removal the system must do.
Is an air-side economizer practical for a data center in Richmond, Virginia?
Direct air-side economizing is harder in Richmond than in drier climates because summer dew points sit well above the 59°F ceiling of the ASHRAE recommended envelope, and the economizer season is shorter than in Loudoun. It can still pay in cool months with good filtration and humidity control. Indirect evaporative units and water-side economizers usually deliver more reliable savings for Richmond and Henrico campuses, and Paul compares them against the site’s weather before recommending one.
Who services cooling plants for data centers in Virginia Beach and Hampton Roads?
Paul Industries services and retrofits cooling plants for data centers in Virginia Beach, Norfolk, Chesapeake and across Hampton Roads, including chillers, towers, dry coolers, pumps and controls. Coastal sites need attention to coil corrosion, fastener materials and tower drift, so Paul’s maintenance plans there include coil inspection and cleaning intervals suited to salt air. Call 201-450-8280 or request a quote with equipment lists and current issues.
What happened in the Northern Virginia data center disconnect?
On July 10, 2024 a fault on a 230 kV line in Northern Virginia triggered about 60 data centers to switch to backup power at once, removing roughly 1,500 MW of demand from the grid in seconds. Grid operators had to act quickly to rebalance the system. For cooling plants, the lesson is that transfers to generator can happen together across a region, so every plant needs a tested restart path rather than assuming the grid will hold.
How should cooling controls respond to a Virginia data center power outage?
Pumps and CRAH fans should keep moving water and air from UPS or the first generator step, while stored cold water carries the heat until chillers restart. The controls should restart chillers one at a time, check that each has stabilized before the next starts, and hold economizer valves in a safe position. Paul writes these sequences, tests them under load during commissioning and documents the expected recovery time for the owner’s operations team.
Does Virginia's energy code limit cooling energy for data centers?
The Virginia Energy Conservation Code, part of the 2021 Uniform Statewide Building Code effective January 18, 2024, is based on the 2021 IECC, which directs data center mechanical systems to the mechanical load component limits of ASHRAE 90.4. Designers demonstrate compliance with an annualized calculation for the climate zone. Paul’s energy models for new plants and major alterations are prepared so the engineer of record can carry them into the code submission.
How much does it cost to cool a data center in Virginia each year?
Energy dominates. At Virginia’s 2024 industrial average of 8.99 cents per kilowatt-hour, every kilowatt of continuous cooling load costs about $788 a year, so a 10 MW hall with a mechanical overhead of 0.25 spends close to $2 million a year on cooling energy before water, treatment and maintenance. Actual tariffs vary. Improving plant efficiency is usually a bigger controllable saving than anything else a Virginia operator can change in the cooling budget.
Can an older chilled water plant in Loudoun County be upgraded without a shutdown?
Paul Industries upgrades operating plants in phases: adding isolation valves during planned low-load windows, hot-tapping new connections, installing temporary chillers or bypasses where needed, and replacing equipment one unit at a time while redundancy covers the load. A method of procedure is written and approved for each step. Economizer heat exchangers, variable-speed drives and controls upgrades are typical first moves in older Loudoun plants.
How do I choose between N+1 and 2N cooling for a Virginia campus?
Start with the tenant commitments and the failure you must survive. N+1 covers the loss of any single machine, which suits most enterprise and many colocation halls; 2N covers the loss of a whole plant or distribution path and is chosen where contracts or risk tolerance demand it. A distributed design can approach 2N resilience with less equipment. Paul prices each option with its piping and controls so the decision rests on full cost.
Which heat rejection equipment keeps a Prince William County data center within sound limits?
Low-speed, large-diameter fans, variable-speed drives that slow fans for most of the year, and siting that puts the yard behind the building, away from neighboring homes, all reduce sound at the property line. Dry coolers and towers with acoustic attenuation are generally easier to keep quiet than banks of rooftop air-cooled chillers. Paul selects and arranges equipment with the project’s sound model so the cooling plan and the county review agree.
Does Paul Industries supply cooling equipment for Virginia projects without installing it?
Paul Industries supplies chillers, plate heat exchangers, pumps, prefabricated pump skids and fabricated pipe spools for Virginia data center projects on a supply-only basis, with submittals, factory test records and startup assistance documented. Owners and general contractors use this route when an installer is already engaged. The same equipment can be supplied with complete installation if the scope grows.
What glycol concentration do Virginia dry coolers need?
The concentration depends on the coldest temperature the fluid can see. Dulles records a 99.6% heating design of 9°F and a median extreme low near minus 1°F, and mountain sites in western Virginia run colder. Too little glycol risks burst coils; too much cuts heat transfer and raises pump energy. Paul sets the mix from the site’s extreme lows, a safety margin and the owner’s choice between freeze and burst protection.
What should a Virginia data center send for a cooling plant quote?
Send the IT load and its phasing, the redundancy target, the site address, any existing plant equipment lists, utility capacity and water supply details, and drawings if they exist. For retrofits, include current chilled water temperatures, trend logs and known problems. With that, Paul Industries can give a budget range from comparable plants and a firm price once the design basis is fixed. Call 201-450-8280 or request a quote.
Sizing a cooling plant for a Virginia data hall?
Send the IT load, redundancy target, site location and any existing plant details, and Paul Industries will return a budget range and a plan for the work. Call 201-450-8280 or request a quote.