Paul Industries designs, builds and services ultrapure water systems in Illinois for pharmaceutical and biologics plants, nuclear and fossil power stations, universities, national laboratories, hospitals and electronics makers, from pretreatment and reverse osmosis through electrodeionization, polishing and distribution loops. Illinois sites draw feedwater from two very different sources, treated Lake Michigan water across the Chicago region and deep wells elsewhere, and the right treatment train starts with knowing which one feeds the plant. Paul Industries delivers design-build systems, complete installation of owner-specified equipment, and supply-only skids.

Request a quote or call 201-450-8280

Headquarters 256 Shore Drive, Kilmarnock, Virginia
Lake Michigan feed Hardness about 144 mg/L as CaCO3; chlorine disinfection (2025 report)
Deep well feed Naturally elevated radium and barium in northern Illinois sandstone aquifers (USGS)
State vessel rule Demineralizers exempt from inspection under 430 ILCS 75/5(b)(9)
Nuclear makeup demand 11 reactors at 6 plants, more than any other state (EIA)
Reviewed November 2026

Where are ultrapure water systems in Illinois used?

Ultrapure water systems in Illinois serve four main groups of users: drug and biologics manufacturers around the North Shore and the western suburbs, power stations that need demineralized boiler and reactor makeup, research institutions from the national laboratories in Lemont and Batavia to university campuses in Chicago, Evanston and Champaign-Urbana, and manufacturers of electronics, coatings and specialty chemicals. Each group defines purity differently, which sets how far the treatment train must go.

The pharmaceutical side is growing. In North Chicago, AbbVie’s February 2026 plan puts $380 million into two new plants for active ingredients on its existing campus, building from spring 2026 toward full operation in 2029. Power is the state’s other large user: Illinois has 11 nuclear reactors at six plants, more than any other state, and every one of them consumes demineralized water of very high purity for makeup. The national picture of uses and grades is on the ultrapure water systems page.

Illinois users of ultrapure water and the quality each typically specifies
UserWhere in IllinoisTypical quality targetSystem emphasis
Pharmaceutical and biologics plantsNorth Shore, Lake County, western suburbsUSP Purified Water and Water for Injection, with UPW for labs and some processesSanitary construction, microbial control, validation records
Nuclear and fossil power stationsStatewide, from the Rock River valley to the Illinois River and downstateDemineralized makeup to plant chemistry limits for conductivity, silica and sodiumHigh recovery, robust pretreatment, continuous analyzers
National laboratories and universitiesLemont, Batavia, Chicago, Evanston, Champaign-UrbanaASTM Type I for instruments; process UPW for detectors and cooling loopsCentral loops plus point-of-use polishers
Hospitals and clinical labsChicago medical districts and regional centersClinical laboratory reagent water; feed for sterile processingReliability, sanitization, compact footprint
Electronics, coatings and specialty chemicalsNorthwest suburbs, Fox Valley, RockfordLow ionic and particle levels set by the product, up to SEMI F63 for semiconductor workPolishing, particle control, low-TOC loop materials

How should an ultrapure water system be designed for Lake Michigan feedwater?

An ultrapure water system designed for Lake Michigan feedwater starts from a moderately hard, chlorinated surface water: the DuPage Water Commission, which buys its water from Chicago, reported hardness of about 144 milligrams per liter as calcium carbonate in its 2025 data, roughly 8 grains per gallon, with chlorine as the disinfectant and sulfate near 27 milligrams per liter. Chicago’s own laboratory analyses over the years show hardness mostly in the 130s and low 140s.

That feed calls for a fairly conventional pretreatment: multimedia or ultrafiltration to handle turbidity and organics that rise with lake turnover and storms, chlorine removal by activated carbon or sodium bisulfite ahead of the membranes, and softening or antiscalant to protect the reverse osmosis stage from calcium carbonate and calcium sulfate scale. Because the disinfectant is free chlorine rather than chloramine, carbon beds remove it readily, though they need sanitization to keep bacteria from colonizing them once the chlorine is gone.

Lake water also changes with the seasons. Temperature falls through the winter, and reverse osmosis output falls with it, commonly estimated at around 3 percent per degree Celsius, so a plant sized on summer water can come up short in February. Paul Industries sizes membranes on cold-water output or adds a feed heat exchanger, and sets the cleaning and monitoring plan for the spring and autumn periods when organics and turbidity tend to rise.

Well water, radium and barium: treating northern Illinois groundwater

Northern Illinois groundwater from the deep sandstone aquifers carries naturally elevated radium and barium, according to the U.S. Geological Survey, along with hardness, iron and dissolved solids that rise with depth. A site on that kind of well, or on a municipal system that draws from it, needs an ultrapure water treatment train built around those constituents rather than around lake water.

Barium matters to reverse osmosis because barium sulfate is one of the least soluble scales a membrane can face; even small concentrations limit recovery and call for an antiscalant chosen for it. Radium is removed by softening resins and by reverse osmosis, which concentrates it in brine, regeneration waste and spent media, so the waste handling plan has to account for it. Iron and manganese need removal ahead of the membranes. Joliet, one of the cities that has treated its groundwater for radium, is joining five neighbors to buy Lake Michigan water from Chicago from 2030 because the aquifer could not meet peak demand; plants in those towns will see their feedwater change from well to lake, and their pretreatment should be reviewed before the switch.

Illinois feedwater sources and how each shapes the treatment train
FeedwaterMain concernsPretreatment responseDownstream effect
Lake Michigan via Chicago or a water commissionModerate hardness, free chlorine, seasonal organics and cold winter waterFiltration or ultrafiltration, carbon or bisulfite dechlorination, softening or antiscalantRO sized for cold water; TOC reduction for organics
Deep sandstone wells, northern IllinoisHardness, iron, dissolved solids, radium and bariumIron removal, softening, barium-specific antiscalant, limited recoveryWaste plan for radium-bearing brine and spent media
Shallow wells and river-influenced supplies, central and southern IllinoisHardness, iron, nitrate, seasonal variationIron removal, softening, multimedia filtrationRecovery and cleaning frequency set by seasonal swings
Towns changing source by 2030Feed chemistry changing from well to lakeReview of softening, antiscalant and dechlorination before the switchMembrane performance and cleaning plan reset

The ultrapure water production train after pretreatment

Ultrapure water production after pretreatment follows the same stages in Illinois as elsewhere: two-pass reverse osmosis or reverse osmosis followed by electrodeionization to remove most dissolved ions, then a polishing stage of ultraviolet oxidation for organics, mixed-bed ion exchange, degasification where dissolved oxygen matters, and ultrafiltration or a final ultrapure water filter at the loop to remove particles. The polishing loop recirculates continuously so the water never stands still in the pipe.

The finish point is set by the ultrapure water specification for the use. Ultrapure water resistivity approaches the theoretical 18.2 megohm-centimeters at 25 degrees Celsius, the same as an ultrapure water conductivity of about 0.055 microsiemens per centimeter, and organic carbon, particles, silica, bacteria and dissolved oxygen are each held to their own limits. Ultrapure water pH is not a useful control measurement at that purity, because the water carries almost no buffering capacity and readings drift as carbon dioxide dissolves from the air; conductivity and resistivity measured online in the loop do the work instead.

Ultrapure water treatment stages and what each does with Illinois feedwater
StageWhat it removes or controlsIllinois note
Multimedia filtration or ultrafiltrationSuspended solids, turbidity, some organicsSized for lake turnover and storm events on Lake Michigan feed
Activated carbon or bisulfite dosingFree chlorine and some organicsChicago-area water is chlorinated, so this stage protects every membrane downstream
Softening or antiscalantHardness ions and scale-forming compoundsBarium-specific antiscalant on deep-well feed; radium captured in resin and brine
Reverse osmosis, one or two passesMost dissolved salts, organics, bacteria and particlesMembrane area sized for cold winter water
ElectrodeionizationRemaining ions, including weakly charged silica and carbon dioxide speciesNeeds stable RO permeate, which seasonal feed swings can upset
UV oxidation at 185 nmOrganic carbon, broken into ionic fragments for removalPaired with mixed-bed polishing after it
Mixed-bed polishingFinal trace ions, bringing resistivity toward theoreticalResin replacement interval set by RO and EDI performance
DegasificationDissolved oxygen and carbon dioxideUsed where power, electronics or specific processes require it
Ultrafiltration or final filterParticles and, for biology uses, endotoxinInstalled at the loop supply or at each point of use

Type 1 ultrapure water for Illinois university and hospital labs

Type 1 ultrapure water, the highest reagent grade in ASTM D1193, is what university, hospital and national laboratory instruments call for, and many Illinois campuses produce it with a central purified water loop feeding point-of-use polishers in each lab. A laboratory ultrapure water system on that model keeps the central plant simple and puts the final purity where it is used, with each polisher’s ultrapure water quality monitored at its own outlet.

Ultrapure water for laboratory benches, HPLC and cell work

Ultrapure water for laboratory benches covers several distinct needs. Ultrapure water for HPLC and mass spectrometry needs very low organic carbon so it does not add background peaks; ultrapure water for molecular biology needs to be free of nucleases and endotoxin, usually with ultrafiltration at the outlet; and ultrapure water for cell culture adds endotoxin and bacterial limits. Paul Industries specifies the polisher and final filter for each use and sets sampling to match.

Electronics and semiconductor work

Ultrapure water for semiconductor manufacturing follows SEMI F63 and the fab’s own limits, which are tighter than laboratory grades for particles, metals, silica and dissolved oxygen. Illinois has electronics and component makers rather than large wafer fabs, so most of the state’s electronics work calls for high-quality rinse water at the product’s own specification; Paul Industries designs to whichever limit the customer’s process documents set.

Demineralized water for Illinois power stations

Demineralized water for Illinois power stations is ultrapure water by another name: nuclear reactors and high-pressure boilers need makeup with very low conductivity, sodium, chloride and silica to protect fuel cladding, steam generators and turbines from corrosion and deposits. With 11 reactors at six nuclear plants, along with gas-fired and remaining coal-fired units and many industrial boilers, Illinois carries steady demand for makeup systems and the service that keeps them in specification.

Power plant makeup trains favor high recovery, rugged pretreatment and continuous analyzers that feed the plant’s chemistry program, which follows the utility’s own water chemistry guidelines. Paul Industries builds and upgrades those trains, replaces aging ion exchange plants with membrane systems, and ties new equipment into plant controls. Boiler-side work at industrial plants is covered on boiler repair in Illinois.

Illinois rules that touch an ultrapure water plant

Illinois rules touch an ultrapure water plant at several points, starting with the Boiler and Pressure Vessel Safety Act, whose Section 5(b)(9) exempts water conditioning equipment, including water softeners, filters, dealkalizers and demineralizers that treat water by means other than heat, from the Act’s inspection sections. Pressure vessels in the treatment train therefore sit outside the State Fire Marshal’s inspection cycle, though they are still built and rated for their service.

The potable side is a different matter. Connections from the public water supply to the treatment plant, backflow prevention and drainage fall under the Illinois Plumbing Code and the Plumbing License Law, under which plumbing is reserved to plumbers holding an Illinois plumbing license. Discharges of reverse osmosis concentrate, regeneration waste and cleaning solutions go to the sewer under the receiving utility’s pretreatment rules, and radium-bearing residues from well-water plants need a disposal route that fits their activity. Sites drawing large volumes of Lake Michigan water do so within the allocation that the Illinois Department of Natural Resources manages under a federal court cap on the state’s diversion. Paul Industries designs the plant’s connections and waste streams to the rules where the plant sits.

Adding capacity to a running Illinois water plant

Adding capacity to a running Illinois water plant is a common project as North Shore drug makers add buildings, research campuses add labs and power stations replace aging demineralizers. The plant has to keep supplying water of full quality while new trains, tanks or loop sections are installed, so the work is planned around isolation points, temporary supply and the quality checks that release each new section into service.

Paul Industries starts with a survey of the existing system and its records: actual demand peaks, how far the current trains are from their limits, the condition of membranes and resins, and where the loop can be isolated. New skids are built and tested before they arrive, so field time is spent on connections. Loop extensions are installed behind closed valves, pressure tested, cleaned, sanitized and sampled until they meet the same water quality as the running loop, and only then opened to it. For regulated plants, each change follows the site’s change control and is documented for its quality records.

Concentrate, regeneration waste and water recovery

Concentrate from reverse osmosis, regeneration waste from softeners and ion exchange, and spent cleaning solutions make up most of the waste from an ultrapure water plant, and in Illinois each stream goes to the receiving sewer utility under its pretreatment and discharge rules. The volume matters as much as the chemistry: a plant running at 75 percent recovery sends a quarter of its feed to drain, which the site pays for twice, once as purchased water and again as sewer charges.

Recovery can be raised with a second-stage or concentrate-recovery RO where scaling chemistry allows, and concentrate can often be reused where lower-quality water is acceptable, such as cooling tower makeup, which links an ultrapure plant to the cooling systems on the same campus. On deep-well feed, barium and radium limit how far recovery can go and decide where concentrated residues may be sent. Paul Industries models recovery, scaling and waste quality together so the owner sees the water bill, the sewer bill and the disposal route for each design option.

Loops, materials and sanitization in Illinois plants

Distribution loops carry ultrapure water from the polishing stage to every point of use and back, and their materials, joining and sanitization method decide whether the water arrives as clean as it left. Pharmaceutical loops are usually electropolished 316L stainless steel built to ASME BPE with orbital welds and hot water or ozone sanitization; electronics and laboratory loops often use PVDF or other high-purity polymers that leach little organic carbon; power plant makeup headers are commonly stainless.

Paul Industries builds stainless loops to the practices described on sanitary process piping in Illinois, passivates them as covered on passivation services in Illinois, and qualifies regulated systems under validation and commissioning in Illinois. Pharmaceutical Purified Water and Water for Injection systems for the same plants are covered on high-purity water systems in Illinois, and general deionized water service on industrial DI water systems.

Keeping bacteria out of an Illinois ultrapure loop

Bacteria control in an Illinois ultrapure loop depends on keeping water moving, keeping it hot or ozonated where the design calls for it, and sanitizing on a schedule set by trend data rather than habit. Dead legs, slow returns and storage tanks with poor turnover give biofilm a place to start, and once biofilm forms it sheds bacteria and organic carbon into the loop no matter how good the polishing stage is.

The design measures are well established: return velocity high enough to scour the pipe, drops kept short, sample valves and instruments mounted without stagnant pockets, tanks with spray balls and vent filters, and sanitization by hot water, ozone or chemical means compatible with the loop material. Illinois adds one seasonal factor, since lake water carries more organic load in spring and autumn, which feeds bacteria downstream if pretreatment lets it pass. Paul Industries sets sampling points and alert levels at startup, reviews the counts with plant staff over the first months of operation, and adjusts the sanitization interval to what the data show. Removing dead legs from older loops, described under dead leg elimination, often does more for counts than any change to the treatment train.

Ultrapure water system cost in Illinois: equipment, water and power

Ultrapure water system cost in Illinois depends on flow rate and storage, the feedwater source and the pretreatment it demands, the finish quality and how many polishing stages it takes, loop length and material, redundancy, instrumentation, and validation requirements in regulated plants. A well-water site with barium and radium carries more pretreatment and waste handling than a Lake Michigan site of the same size; a stainless sanitary loop with validation costs more than a polymer loop for a lab.

Operating cost follows water, power and consumables. Reverse osmosis rejects part of its feed as concentrate, so recovery affects both water purchases and sewer charges; pumps and UV lamps draw power priced near the state’s 2024 industrial average of 8.83 cents per kilowatt-hour; and membranes, resins, filters and lamps need replacing on schedules set by the feed. Paul Industries prices the ultrapure water equipment and installation after reviewing a feedwater analysis and the use list, and shows the expected ultrapure water price per thousand gallons produced alongside the capital figure so the owner can compare options on lifetime cost.

Who builds ultrapure water systems for Illinois plants and labs?

Paul Industries builds ultrapure water systems for Illinois plants and labs. From its home office at 256 Shore Drive in Kilmarnock, Virginia, this East Coast company takes ultrapure water design, fabrication, installation, startup and service work throughout Illinois, in all 50 states and at plants outside the United States. Skids are built and tested before shipment, loops are installed and passivated on site, and systems are started up, sampled and handed over with full records.

The headquarters-state version of this work is on ultrapure water systems in Virginia, a comparison with Great Lakes and upstate feedwater on ultrapure water systems in New York, and the regional picture on the Midwest page. Piping between the water plant and other utilities is covered on process piping in Illinois.

Ultrapure water from Paul Industries across Illinois

Paul Industries delivers ultrapure water systems across Illinois: feedwater review, design, skid fabrication, loop installation, passivation, startup, qualification records for regulated plants and long-term service. Send a recent feedwater analysis or the name of the water supplier, the flow and quality required at each point of use, the loop layout and any validation needs. Process, piping and utility work elsewhere in the state is listed on the Illinois page. Call 201-450-8280 or request a quote.

Standards referenced: ASTM D1193 · ASTM D5127 · SEMI F63 · USP Purified Water and Water for Injection monographs · EPRI water chemistry guidelines · Illinois Boiler and Pressure Vessel Safety Act (430 ILCS 75) · Illinois Plumbing Code (77 Ill. Adm. Code 890) · ASME BPE

Frequently asked questions

Who builds ultrapure water systems for pharmaceutical plants on the North Shore and in Lake County?

Paul Industries builds ultrapure and high-purity water systems for pharmaceutical and biologics plants on the North Shore and across Lake County, including sanitary stainless loops, polishing stages and the records regulated plants keep. New active ingredient capacity in North Chicago adds demand for water systems in the area. Paul Industries designs each system to the plant’s own quality and validation requirements.

Does Paul Industries install ultrapure water systems in Chicago labs and hospitals?

Paul Industries installs ultrapure water systems in Chicago laboratories, hospitals and university buildings, often as a central purified water plant feeding point-of-use polishers in each lab. Work in occupied buildings is staged around research and clinical schedules, with new loop sections tested and sanitized before they connect. Feedwater in Chicago is chlorinated Lake Michigan water, which sets the pretreatment design.

Who installs ultrapure water systems for research sites in Lemont, Batavia and Champaign-Urbana?

Paul Industries installs ultrapure water systems for national laboratory, university and research sites in Lemont, Batavia, Champaign-Urbana and elsewhere in Illinois, including process water for detectors and cooling loops as well as Type 1 lab water. Feedwater at these sites ranges from Lake Michigan water to deep wells. Paul Industries reviews the feedwater analysis first and designs pretreatment around it.

Can Paul Industries build demineralized makeup systems for Illinois power plants?

Paul Industries builds and upgrades demineralized makeup systems for Illinois nuclear, gas and industrial power plants, including reverse osmosis, electrodeionization and mixed-bed polishing, with continuous analyzers tied to plant controls. Upgrades are staged so the existing plant keeps supplying makeup until the new train is proven. Paul Industries designs to the chemistry limits the plant operator sets.

Which ultrapure water purification system suits a North Shore pharmaceutical plant?

A North Shore pharmaceutical plant on Lake Michigan water usually needs dechlorination, softening or antiscalant, two-pass reverse osmosis or RO with electrodeionization, and a sanitizable stainless loop, with ultrapure polishing where labs or specific processes call for it. Pharmacopeial Purified Water and Water for Injection may come from the same pretreatment. Paul Industries sets the train from the plant’s quality and validation needs.

What does Lake Michigan hardness mean for RO in the Chicago suburbs?

Lake Michigan water delivered through Chicago and the DuPage Water Commission had hardness of about 144 milligrams per liter as calcium carbonate in 2025 data, about 8 grains per gallon, which is moderately hard. Reverse osmosis needs softening or an antiscalant to run at good recovery on that feed. Paul Industries runs scaling projections on the actual analysis before setting recovery.

Which disinfectant arrives in Chicago-area water, and how does an ultrapure plant handle it?

Water from Chicago and the DuPage Water Commission is disinfected with chlorine, according to the 2025 water quality data. Free chlorine damages polyamide RO membranes, so it must be removed first, and activated carbon or sodium bisulfite remove it readily. Carbon beds then need sanitization to control bacteria. Paul Industries designs dechlorination and monitoring to suit the supplier’s disinfectant.

Why do radium and barium matter for a northern Illinois well-water RO plant?

Deep sandstone aquifers in northern Illinois carry naturally elevated radium and barium. Barium forms barium sulfate scale that limits RO recovery even at low levels, so antiscalant choice and recovery are set around it. Radium concentrates in RO brine, regeneration waste and spent media, which affects disposal. Paul Industries designs pretreatment and waste handling from the well analysis.

What happens to a Joliet-area ultrapure water plant when the city switches to Lake Michigan water?

Joliet and five neighboring towns plan to switch from groundwater to Lake Michigan water bought from Chicago from 2030, so plants in those towns will move from hard, mineral-rich well water to chlorinated lake water. Softening, antiscalant, dechlorination and RO recovery should be reviewed before the change. Paul Industries reviews the new feed analysis and adjusts or replaces pretreatment as needed.

Do ultrapure water vessels need Illinois State Fire Marshal inspection?

Water conditioning equipment such as softeners, filters, dealkalizers and demineralizers is exempt from the inspection sections of the Illinois Boiler and Pressure Vessel Safety Act under Section 5(b)(9), so treatment train vessels are generally outside the State Fire Marshal’s inspection cycle. Heated vessels such as hot water sanitization tanks need separate review. The turnover file from Paul Industries notes which vessels fall under that exemption.

What ultrapure water quality should a lab polisher deliver?

A lab polisher typically delivers Type 1 water with resistivity close to 18.2 megohm-centimeters at 25 degrees Celsius, low organic carbon, and bacterial and particle limits set by the lab’s work, with endotoxin and nuclease limits for biology. The central loop feeding it is usually purified water of lower grade. Paul Industries sets the polisher, final filter and sampling plan for each lab’s use.

How is ultrapure water conductivity monitored in an Illinois loop?

Conductivity and resistivity are measured continuously with online cells at the polishing outlet and the loop return, using temperature compensation designed for very pure water, since grab samples absorb carbon dioxide and read high. Organic carbon, particle and dissolved oxygen analyzers are added where the specification calls for them. Paul Industries installs, calibrates and records the analyzers at startup.

Why does an Illinois ultrapure plant make less water in January?

Winter lowers feedwater temperature, and RO output falls as water cools, so a plant sized on summer water can fall short in winter. Outdoor tanks and piping need freeze protection, and building heat must keep treatment rooms above freezing. Paul Industries sizes membranes on cold-water output or adds feed heating, and includes freeze protection for any exposed equipment.

What does it take to lift an Illinois purified water system to ultrapure quality?

An existing purified water system can usually be upgraded by adding polishing stages such as UV oxidation, mixed-bed ion exchange, degasification and ultrafiltration, and by replacing loop sections whose materials add organics or particles. The pretreatment and RO must be sound first. Paul Industries surveys the current system, tests its water and proposes a staged upgrade that keeps supply running.

Which turnover documents does an Illinois ultrapure water project deliver?

A new system comes with design documents, equipment data, weld and passivation records for stainless loops, pressure test and sanitization records, analyzer calibrations, startup water quality results, operating and maintenance manuals, and, for regulated plants, installation and operational qualification records. Paul Industries assembles them in one turnover package keyed to the system drawings.

How is an Illinois ultrapure water system kept in specification after startup?

An ultrapure water service agreement from Paul Industries keeps membranes clean and renewed, swaps resins, cartridges and UV lamps on schedule, calibrates analyzers, sanitizes the loop, and reviews sampling trends, with seasonal checks for winter output and spring organics. Agreements cover systems Paul Industries built and existing systems alike, with records kept in a format plant quality teams can file.

What information starts an ultrapure water quote for an Illinois site?

Helpful inputs are a recent feedwater analysis or the water supplier’s name, the flow and quality needed at each point of use, peak and average demand, the loop layout or building drawings, any validation requirements, and the waste discharge route. Paul Industries returns a treatment train proposal, a budget range and an operating cost estimate from that information.