Paul Industries provides boiler repair in New Hampshire for hospitals, universities, biologics and food plants, mills and public buildings, repairing pressure parts, burners, controls and trim on power, high temperature and heating boilers covered by RSA 157-A. New Hampshire inspects boilers through its Department of Labor, and the statute and the Lab 1200 rules decide how a failed inspection turns into repair work, who hears when the work is finished and when the unit returns to service. Paul Industries plans every repair around those steps and around a heating season that runs from October well into spring.

Request a quote or call 201-450-8280

Headquarters 256 Shore Drive, Kilmarnock, Virginia
New Hampshire law RSA 157-A, administered by the Department of Labor
Rules Lab 1200, readopted effective September 19, 2026
Power boilers Certificate inspection every year, external under pressure
After a failed inspection Owner notifies the commissioner and inspector once repairs are done
Air permit trigger 10 MMBtu/h on gas or distillate oil (Env-A 607.01)
Reviewed November 2026

What does boiler repair in New Hampshire cover under RSA 157-A?

Boiler repair in New Hampshire covers any work that restores a boiler’s pressure parts, firing equipment or safety devices, because RSA 157-A writes the controls into the definition of a boiler. The statute’s definition takes in the closed vessel, the apparatus that generates the heat and all controls and safety devices associated with it. A flame safeguard replacement, a new low-water cutoff or a rebuilt feedwater regulator is therefore boiler work in the eyes of the law, alongside tube, drum and header repairs.

The chapter sorts boilers into pressure classes, and the class sets the inspection rhythm that produces most repair findings. A power boiler makes steam or vapor above 15 psig. A high pressure, high temperature boiler heats water or another fluid above 160 psig or above 250 degrees F. A low pressure boiler is a steam boiler at 15 psig or less, or a hot water heating boiler at no more than 160 psig and 250 degrees F. Water heaters installed with no more than 200,000 Btu per hour of heat input and 210 degrees F water, boilers under 200,000 Btu per hour output in apartment houses, boilers under federal or Coast Guard control and qualifying hobby boilers sit outside the chapter.

How RSA 157-A classes the boilers New Hampshire sites repair
ClassWhere the statute draws the lineTypical repair workWhat the owner keeps afterward
Power boilerSteam or other vapor generated above 15 psigWaterwall and generating tube replacement, drum and header weld repairs, retubing, safety valve workNational Board R-1 report, weld and examination records, hydrostatic test record, new certificate
High pressure, high temperature water boilerWater or other fluid above 160 psig or above 250 degrees FTube and header repairs, circulation and expansion fixes, relief valve replacementSame records as a power boiler, plus the relief valve set pressure and capacity
Low pressure steam boilerSteam at 15 psig or lessFiretube retubes, gasket and handhole work, low-water cutoff and pressure control replacementRepair record, control test sheet, certificate after reinspection
Hot water heating or supply boilerNo more than 160 psig and 250 degrees FTube leaks, burner and control rebuilds, relief valve and expansion tank workRepair record, combustion readings, certificate after reinspection
Cast iron sectional boilerHeating or supply boiler built of cast iron sectionsSection replacement, nipple and gasket repairs, burner workSection and pressure test record, certificate after reinspection
Units outside the chapterSmall water heaters, small apartment boilers, federal units, qualifying hobby boilersThe same mechanical repairs, without a state certificateASME and manufacturer records, fuel gas and building code paperwork

How a failed New Hampshire boiler inspection becomes a repair

A failed New Hampshire boiler inspection becomes a repair through a short loop written into RSA 157-A:9-a. After each inspection, the inspector files a report with the Commissioner of Labor saying whether the boiler is certifiable and passes the result to the owner. When a boiler fails, the inspector also hands the owner an abstract of the statutory requirements and the recommendations for the repairs that will correct the deficiency.

After an NH boiler inspection that ends in a failed result, the owner, or the owner’s designee, notifies both the commissioner and the inspector once the repair or replacement is complete, and the boiler is reinspected at the discretion of the inspector or the commissioner before a new certificate is furnished. A certificate carries a $50 fee under the statute and becomes void if the fee is unpaid 30 days after it is issued, so the accounts payable step belongs on the same checklist as the hydrostatic test.

That loop makes the inspector’s recommendations the working scope for the job. Paul Industries reads the recommendations, opens and examines the boiler to confirm the extent of the damage, and prices a repair that answers each listed item. When the work is done, Paul Industries prepares the completion notice with the repair records attached, which gives the inspector everything the reinspection needs. Anyone asking what does a boiler inspection consist of under the New Hampshire boiler code will find the answer in that report: construction, installation and condition, checked against the ASME code and the state’s rules, internal where the construction permits.

Welded repairs, alterations and the National Board Inspection Code

Welded repairs and alterations on New Hampshire boilers follow the National Board Inspection Code, which RSA 157-A:3 requires the state’s rules to track and which Lab 1200 has long named as the standard for repairs and alterations. The Department of Labor readopted Lab 1200 with amendments effective September 19, 2026, and the NBIC remains the reference for how a repair is planned, performed, examined and documented. A welded repair is made under the National Board R program with the inspector consulted before work begins, using qualified weld procedures and welders, and the result is recorded on a National Board R-1 report.

An alteration changes the boiler’s design rather than restoring it: a rerate, a new nozzle, an added heating surface or a change in the pressure-retaining parts. The NBIC treats an alteration with design calculations and an R-2 report, and the nameplate data changes with it. RSA 157-A:5 ties the maximum allowable pressure of an existing boiler to the code under which it was built and stamped, and for a boiler that carries no ASME, API-ASME or EN 303-5 symbol, the pressure is computed under the inspection code of the National Board. That last route matters in New Hampshire, where European biomass boilers built to EN 303-5 heat schools, offices and district systems.

Paul Industries assembles the weld procedures, welder qualifications, material test reports and examination plan before the outage, so the boiler opens to a repair that is already planned and documented.

Common repairs on New Hampshire boilers and the record each one produces
RepairCode routeRecord for the owner’s fileCheck before firing
Watertube boiler tube replaced by weldingNBIC repair under the R program, inspector consulted firstR-1 report, weld map, radiography or other examination resultsHydrostatic test as the NBIC and the inspector direct
Firetube boiler retubeNBIC repair, rolled and beaded or welded tube ends to the original designTube material reports, rolling or welding record, R-1 report where requiredHydrostatic test, then a leak check at operating pressure
Drum, shell or header weld repairNBIC repair with a written repair method accepted by the inspectorR-1 report, procedure and welder records, examination reportsHydrostatic test and any additional test the inspector deems necessary
Rerate, added nozzle or heating surface changeNBIC alteration with design calculationsR-2 report, revised nameplate data, design fileTest pressure set by the alteration design
Safety or relief valve replacementReplacement valve matched to set pressure and required relieving capacityValve nameplate data and the capacity calculationSet pressure confirmed against the certificate pressure
Burner, gas train or flame safeguard replacementManufacturer’s instructions; NFPA 85 on single burner boilers of 12.5 MMBtu/h and larger; fuel gas fitting rulesCombustion test sheet, interlock and limit test recordOperational test of every limit, interlock and low-water cutoff

Grace periods, penalties and appeals: the dates around a repair

The dates around a New Hampshire boiler repair start with the certificate interval in RSA 157-A:8, which also answers how often do boilers need to be inspected in the state: power boilers every year and most heating boilers every two years. The statute allows a two-month grace period beyond each interval before the boiler falls out of compliance. Before the grace period ends, the Department of Labor sends the owner a written warning for any required inspection not completed. The commissioner may permit a longer period between certificate inspections, so an owner facing a large repair outage asks the commissioner in writing, with the inspector’s view of the boiler’s condition behind the request.

The penalties explain why owners take those dates seriously. Operating a covered boiler without a valid inspection certificate, or at a pressure above the one on the certificate, is a misdemeanor for a natural person and a felony for any other person under RSA 157-A:10. The commissioner may also impose a civil penalty of up to $500 for each violation of the chapter or its rules after a hearing. An owner who disagrees with an inspector’s order or act has 15 days to appeal to the commissioner, who issues an order within 30 days; anyone aggrieved by the commissioner’s order may petition the county superior court within 30 days after it.

One more rule shapes the repair budget. If the inspector decides a hydrostatic test or another test is necessary, RSA 157-A:8 makes the owner responsible for it. Paul Industries supplies the test pump, calibrated gauges, blanks and test record, and holds the test with the inspector present when the inspector asks to witness it, through its hydrostatic testing work.

Boiler repair, New Hampshire air permits and the fuel behind the burner

Boiler repair work in New Hampshire becomes an air permit question when a burner change, a fuel switch or a replacement unit alters what the plant burns or how much it can fire. NHDES rule Env-A 607.01 requires a temporary permit before installing a new or modified external combustion device of 10 million Btu per hour gross heat input or more on natural gas, propane or distillate oil, 4 million Btu per hour or more on #4 oil, or 2 million Btu per hour or more on solid fuel, residual oil or used oil. Larger industrial boilers also fall under the state’s nitrogen oxide rules in Env-A 1300. A repair that keeps the burner, fuel and firing rate unchanged stays inside the existing permit; a retrofit that changes any of them gets reviewed against it first.

The gas side of a repair carries its own rules. RSA 153:27 defines fuel gas fitting as the installation, repair, alteration and service of the piping, appliances and equipment that carry natural gas or propane from the point of delivery to the combustion zone, including the venting of flue gases. That work falls under the Mechanical Licensing Board, which issues endorsements such as fuel gas installation technician, fuel gas service technician and fuel gas piping installer under RSA 153:29. On single burner boilers of 12.5 million Btu per hour and larger, NFPA 85 sets the burner management and combustion safeguards, which the state fire code brings in through its adoption of NFPA 1.

Paul Industries confirms the plant’s permit conditions and the burner management requirements before it specifies replacement firing equipment, and it hands over combustion readings and interlock test records with the repaired boiler.

Mill, campus and biologics steam: where New Hampshire’s boiler load sits

New Hampshire’s boiler load sits in a handful of large steam plants and in hundreds of heating plants serving hospitals, schools, offices and factories. In Berlin, Burgess BioPower runs a 75 megawatt biomass plant that sells power into the ISO New England markets and emerged from Chapter 11 with a plan that took effect on April 1, 2026. In Durham, the University of New Hampshire’s cogeneration plant, online since 2006, burns processed landfill gas piped 12.7 miles from the Turnkey landfill in Rochester, and the same gas fuels the backup heating plant; waste steam runs absorption chillers in summer.

In Hanover, Dartmouth’s central heating plant burned roughly 3.5 million gallons of No. 6 oil a year in its steam system, and the college is converting campus heating from steam to hot water, with construction under way since June 2024. Conversions of that kind leave existing steam boilers carrying the load while the new system is built in stages, which turns repair decisions on the old units into questions of remaining service years rather than decades. On the Seacoast, biologics manufacturing at the Pease International Tradeport in Portsmouth, where Lonza added 6,000 liter bioreactors in 2018, depends on plant steam for sterilizing vessels and lines and for clean steam generation.

Each setting wears boilers differently. Biomass units erode tubes at fly ash paths and burn through grates and refractory. Campus plants cycle hard between summer and January peaks. Biologics plants carry tight water chemistry and cannot accept unplanned trips during a batch. Paul Industries plans the repair around the plant’s steam balance, the batch or academic calendar and the outage the inspector and the operators can accept.

Boiler service, NH plants and the work between inspections

Boiler service in NH plants keeps a unit ready for its next certificate inspection and through a heating season that can bring weeks below zero in the North Country. For owners asking how often does a boiler need maintenance, the answer depends on the class, the fuel, the run hours and the water chemistry, and the calendar below is a practical starting point for New Hampshire sites. The boiler log is the most useful single record, because a slow rise in stack temperature, makeup water or firing rate shows a developing problem months before a tube fails.

A boiler repair and maintenance calendar for New Hampshire plants
WhenTaskWhy it matters in New Hampshire
Every shiftRecord pressure, water level, stack temperature, firing rate and makeup flow; test the gauge glassLong heating seasons put high run hours on campus and hospital units
Daily to weeklyBottom blowdown and water tests to the treatment program; low-water cutoff test as the manufacturer directsWell water across much of the state brings hardness and iron into makeup
August and SeptemberCombustion tuning, flame safeguard and limit tests, refractory and gasket inspection, spare parts checkA repair found in October leaves time before the January peak
Ahead of the certificate inspectionCool, drain, open and clean fire and water sides; gather the last report and recommendationsThe inspection is internal where the construction permits
Spring shoulder seasonPlanned tube, retube and refractory work on units released from heating dutyCampus and hospital plants run fewer boilers once heating load falls
Summer lay-upWet lay-up with treated water or dry lay-up with desiccantIdle heating boilers pit quickly when left half full of untreated water
After any low-water trip or overfiring eventShut down, inspect for overheating and distortion, contact the inspector before restartA damaged boiler cannot carry a certificate until the defect is corrected

The rest of the program follows the boiler’s history. A unit with steady chemistry and clean reports runs well on the calendar above, while one with repeat tube leaks needs closer attention to treatment, deaeration and operator rounds. Paul Industries links service visits to the plant’s boiler water treatment program and to the certificate dates, so a single service contract covers boiler repair and maintenance on one schedule.

Boiler repair or replacement: what a new unit triggers in New Hampshire

The boiler repair or replacement decision in New Hampshire weighs the remaining life of the pressure parts against the cost and outage of the repair, the fuel and permit position and the code steps a new unit brings. Owners who ask how often do boilers need to be replaced get an answer from the boiler’s condition rather than its age: tube wall thickness, drum and header condition, refractory, burner and control obsolescence, and the efficiency gap against a new unit at New Hampshire fuel and power prices.

A replacement has its own sequence. RSA 157-A:4 bars installing a boiler that does not conform to the applicable codes and the commissioner’s rules for new construction and installation, with a special installation and operating permit available at the commissioner’s discretion for equipment of special design that stays within the spirit and safety objectives of those codes. Boilers other than cast iron sectional units are inspected during construction by an inspector authorized in New Hampshire or commissioned by a state with substantially equal requirements. A used boiler can be sold, reused or reinstalled under RSA 157-A:5 once it conforms to the rules for existing installations and has not been found unsafe.

The building side runs through the State Building Code in RSA 155-A, which adopts the 2024 International Mechanical Code with state amendments, and the state fire code built on the 2024 editions of NFPA 1 and NFPA 101. Paul Industries prices both paths when a boiler reaches this point, with the repair outage and remaining life set against the replacement’s code steps, piping, stack, controls and permit work. Supply-only, design-build and complete installation are all available for a replacement, and the boiler room piping ties into process piping in New Hampshire on the same contract.

Where New Hampshire’s boilers run, from the Seacoast to the North Country

New Hampshire’s boilers run in clear regional clusters, and each brings its own repair pattern. The Seacoast around Portsmouth, Dover and Rochester combines the Pease Tradeport’s biologics and manufacturing tenants with hospitals, the Durham campus and food plants. Manchester and Nashua carry hospitals, the mill buildings of the Millyard, office towers and precision manufacturers, while Merrimack, Bedford, Salem and Londonderry add manufacturing and food production along the Everett Turnpike and I-93. Concord holds state buildings, hospitals and schools.

West and north, the pattern changes again. Lebanon and Hanover combine a medical center and the Dartmouth campus. Keene and the Monadnock region run manufacturing and college plants, and Laconia and the Lakes Region add hospitals, schools and seasonal businesses. Berlin and the North Country carry biomass steam and the coldest design conditions in the state. Power reaches these sites through Eversource, which serves about 70 percent of the state’s retail electric customers, Unitil in the Concord and Seacoast areas, Liberty and the member-owned New Hampshire Electric Cooperative. That matters when a boiler repair involves feedwater pumps, draft fans or electrode boilers that need an electrical outage. Paul Industries takes boiler work in every one of these regions.

Public boiler work and wage rules in New Hampshire

Public boiler work in New Hampshire runs without a state prevailing wage schedule, because the state repealed its public works wage law in 1985. A school district, town or state agency therefore prices a boiler repair on the contract terms it sets, while projects that carry federal funding bring in Davis-Bacon wage determinations on construction contracts over $2,000. Paul Industries prices public boiler work to the funding source named in the bid documents and keeps the weekly payroll reports a federal wage determination requires.

What does boiler repair cost in New Hampshire?

Boiler repair cost in New Hampshire depends on the boiler class and size, the damage found once the unit is open, the NBIC route the repair follows, the tube stock and materials needed and how much outage the plant can accept. A cast iron section or a handful of firetube tubes is a contained job; a waterwall failure on a biomass or campus power boiler can involve tube fabrication, scaffold, refractory, examination, a hydrostatic test and temporary steam. Repairs found in the middle of a cold snap cost more than the same scope planned into the spring shoulder season, which is a strong argument for acting on inspection recommendations early.

The statute adds a few fixed charges. Inspections performed by Department of Labor employees are billed at $100 per hour under RSA 157-A:3-a, and each certificate carries a $50 fee. Boiler replacement cost adds the new unit, the piping and stack work, controls, permits and the inspection during construction. Paul Industries prices repair work with labor, materials, examination, testing and temporary equipment listed separately, offers a budget range from comparable scope before the boiler is opened, and confirms a firm price once the inspection defines the repair.

Who repairs boilers in New Hampshire?

Paul Industries repairs power, high temperature and heating boilers across New Hampshire for hospitals, campuses, biologics and food plants, mills and public buildings. Paul Industries is an East Coast contractor headquartered at 256 Shore Drive, Kilmarnock, Virginia, formerly based in northern New Jersey and then Pennsylvania, and it takes boiler work across New Hampshire, in all 50 states and at plants outside the United States through its international work. For a plant comparing boiler inspection requirements by state, the New Hampshire answer is RSA 157-A and Lab 1200, and Paul Industries plans the repair, the paperwork and the return to service around them.

The same scope runs across New England: boiler repair in Massachusetts and boiler repair in Connecticut under those states’ laws, and boiler repair in Virginia in the headquarters state. The national boiler repair page covers methods by boiler type, and the New Hampshire page covers the state’s wider process work. Related New Hampshire work includes pressure vessel fabrication in New Hampshire for the deaerators, blowdown tanks and receivers in a boiler room, industrial welding services in New Hampshire and chiller repair in New Hampshire for the cooling side of the same plants.

Boiler repair from Paul Industries for New Hampshire sites

Paul Industries handles boiler inspection and repair follow-through for New Hampshire owners as one job: diagnosis, tube and pressure part repairs, retubing, refractory, burner and control rebuilds, safety valve replacement, alterations and replacement boilers, with the NBIC records, the hydrostatic test and the completion notice to the commissioner and the inspector. Send the boiler’s state number, the last inspection report and the inspector’s recommendations, and request a quote for the repair.

Standards referenced: RSA 157-A, Boilers and Pressure Vessels Law · N.H. Admin. Code Lab 1200, Boilers and Pressure Vessels (readopted effective September 19, 2026) · ASME Boiler and Pressure Vessel Code · National Board Inspection Code (NB-23) · EN 303-5 (biomass heating boilers) · NFPA 85, Boiler and Combustion Systems Hazards Code · N.H. Admin. Code Env-A 607.01 and Env-A 1300 (NHDES air permits and NOx rules) · RSA 153:27 to 153:29 (fuel gas fitting and the Mechanical Licensing Board) · New Hampshire State Building Code, RSA 155-A (2024 International Mechanical Code) · New Hampshire State Fire Code, RSA 153:1 (NFPA 1 and NFPA 101, 2024 editions)

Frequently asked questions

Who handles commercial boiler repair, NH Seacoast plants in Portsmouth, Dover and Rochester included?

Paul Industries handles commercial boiler repair across the Seacoast, including Portsmouth, the Pease International Tradeport, Dover, Rochester and Durham. Biologics and manufacturing tenants at Pease run steam for sterilization and process heat, so repairs are planned around batch schedules and the plant’s steam balance. Hospitals and schools in the area run heating boilers that carry biennial certificates under RSA 157-A. Call 201-450-8280 with the boiler’s details.

Does Paul Industries provide boiler service, Manchester NH hospitals and Millyard buildings included?

Paul Industries provides boiler service and repair for hospitals, office towers, schools and the converted mill buildings of Manchester’s Millyard. Many Millyard buildings now house laboratories and regenerative manufacturing tenants that depend on steady heat and humidity, so planned work is scheduled for the spring and summer shoulder seasons. Paul Industries also covers Nashua, Merrimack and Bedford sites on the same terms.

Does Paul Industries handle boiler service, Concord NH state buildings and hospitals included?

Paul Industries services and repairs boilers for state buildings, hospitals, schools and manufacturers in Concord and the surrounding capital region. Public owners there often run several heating boilers on a common header, and the repair plan keeps enough capacity online to heat occupied buildings while one unit is open. Paul Industries prepares the completion notice and repair records the Department of Labor and the inspector need after the work.

Who repairs boilers for campuses and hospitals in Lebanon and Hanover?

Paul Industries repairs boilers for the hospital, college and research buildings of Lebanon and Hanover and the rest of the Upper Valley. Campus plants in the area are moving from steam toward hot water in stages, which keeps existing steam boilers in service during the transition. Paul Industries prices repairs on those units against their planned remaining service so owners spend in proportion to the years left.

Can Paul Industries take boiler and steam plant work in Berlin and the North Country?

Paul Industries takes boiler and steam plant work in Berlin, Gorham, Lancaster and across the North Country, including biomass units, mill steam plants, hospitals and schools. Biomass boilers there see grate, refractory and tube erosion damage, and the region’s cold design conditions call for freeze protection on any line drained for a repair. Paul Industries plans outages so the plant is back on line before the coldest weeks.

Does an apartment building boiler in New Hampshire need a state certificate?

RSA 157-A:6 exempts private residences and apartment houses of fewer than three family units from the inspection requirements, and it leaves boilers with less than 200,000 Btu per hour output in apartment houses outside the chapter. Larger apartment boilers fall inside the law and carry the biennial certificate a heating boiler needs. Paul Industries repairs both groups to the same ASME and fuel gas practice.

What does the inspector's abstract of requirements mean for a New Hampshire repair?

When a boiler fails its inspection, RSA 157-A:9-a requires the inspector to give the owner an abstract of the statutory requirements and recommendations for the repairs needed. That document defines the scope the reinspection checks. Paul Industries prices the repair item by item against it, so each recommendation is answered with a repair record when the owner reports the work complete.

Who tells the Department of Labor that a New Hampshire boiler repair is finished?

The owner or the owner’s designee notifies both the Commissioner of Labor and the inspector once the required repairs are complete, under RSA 157-A:9-a. The boiler is then reinspected at the inspector’s or commissioner’s discretion before a new certificate issues. Paul Industries prepares that notice for the owner with the R report, test record and photos attached.

Can a European biomass boiler built to EN 303-5 be repaired and operated in New Hampshire?

RSA 157-A:5 recognizes the EN 303-5 symbol alongside the ASME and API-ASME symbols when it sets the maximum allowable pressure of an existing boiler, so EN 303-5 biomass boilers operate under the state’s certificate system. Repairs on them follow the National Board Inspection Code with the inspector consulted. Paul Industries repairs pellet and wood chip boilers serving schools, offices and district systems.

What happens if a New Hampshire boiler runs past its two-month grace period?

RSA 157-A:8 allows two months beyond each certificate interval, and the Department of Labor sends a written warning before the grace period ends. Operating after the certificate lapses is operating without a valid certificate, which RSA 157-A:10 makes a misdemeanor for a natural person and a felony for any other person. An owner facing a long repair asks the commissioner in writing for a longer period before the grace period runs out.

How does an owner appeal an inspector's order on a New Hampshire boiler?

Under RSA 157-A:12, an owner aggrieved by an inspector’s order or act may appeal to the Commissioner of Labor within 15 days. The commissioner issues an order approving or disapproving it within 30 days, and anyone aggrieved by that order may petition the county superior court within 30 days. A documented condition assessment from Paul Industries gives the owner technical evidence for that process.

Who pays for a hydrostatic test the New Hampshire inspector asks for?

RSA 157-A:8 places a hydrostatic test or other test the inspector deems necessary on the owner of the boiler. In practice that means the owner arranges the water, pump, gauges, blanks and venting, and the inspector witnesses it when required. Paul Industries supplies all of it as part of the repair and returns a signed test record for the owner’s file.

Which New Hampshire licensing rules reach the gas train during a boiler repair?

RSA 153:27 defines fuel gas fitting to include repair and service of gas piping, appliances and equipment from the point of delivery to the combustion zone, with the flue venting. That work falls under the Mechanical Licensing Board, which issues installation technician, service technician and piping installer endorsements under RSA 153:29. Paul Industries plans gas train, regulator and venting work to those requirements and documents the combustion test afterward.

When does a burner change on a New Hampshire boiler need an NHDES air permit?

Env-A 607.01 requires a temporary permit before a new or modified external combustion device is installed at 10 million Btu per hour or more on gas or distillate oil, 4 million on #4 oil, or 2 million on solid fuel or residual oil. A burner retrofit that changes fuel or firing rate on a unit near those levels needs that review first. Paul Industries checks the permit before specifying equipment.

Can a used boiler from another state be installed at a New Hampshire plant?

RSA 157-A:5 allows the sale, reuse and reinstallation of a boiler once it conforms to the commissioner’s rules for existing installations and has not been found unsafe on inspection. Its maximum allowable pressure follows the code under which it was built and stamped. Paul Industries inspects a used unit’s tubes, shell and records before purchase and handles the move, installation and first certificate inspection.

How often does a hospital or college boiler in New Hampshire need maintenance?

Hospital and college boilers need daily logs and blowdown, weekly control tests, a full combustion and safety device check each late summer, and a lay-up plan for units idle in summer. Power boilers add the annual certificate inspection and the external inspection under pressure. Paul Industries sets those tasks into a service contract matched to the plant’s certificate dates and heating peaks.

Does a New Hampshire boiler certificate need to be posted in the boiler room?

RSA 157-A:9-a requires inspection certificates to be displayed conspicuously in the vicinity of the boiler or vessel. The certificate shows the pressure the boiler may carry, which every repair and rerate is checked against. Paul Industries confirms the posted certificate and nameplate data at the start of each repair so the work and the records match the unit.

What should a New Hampshire owner send to have a boiler repair priced?

Send the boiler’s state number, make, model, year, fuel and class, the current certificate, the last inspection report with any recommendations, recent operating logs, water treatment reports and photos of the damage and nameplate. For campus and plant units, add the steam or heating demand during the outage. Paul Industries uses that file to plan the repair and give a budget range.

Boiler down or carrying an inspector's recommendations in New Hampshire?

Send the boiler’s state number, the last inspection report, the inspector’s recommendations and recent logs. Call 201-450-8280 or request a quote.