Paul Industries provides chiller repair in Pennsylvania for manufacturing plants, hospitals, universities, office buildings and data centers, diagnosing and repairing centrifugal, screw and scroll machines and the towers, pumps and controls around them. Pennsylvania adds its own layer to the work: a state pressure vessel law that treats chillers differently from the vessels beside them, a Philadelphia tune-up mandate that turns plant problems into deadlines, and a climate that runs from humid Delaware Valley summers to cool Lake Erie shores. Paul Industries repairs, overhauls, retrofits and replaces chillers under one contract and keeps the records each of those rules expects.

Request a quote or call 201-450-8280

Headquarters 256 Shore Drive, Kilmarnock, Virginia
State vessel rules Chillers up to 300 psi design, water to 210 F, excluded (34 Pa. Code 3a.3)
Philadelphia tune-ups Buildings of 50,000 sq ft or more, every five years
Summer contrast July normal highs: Philadelphia 87.8 F, Pittsburgh 83 F (NOAA)
Industrial power price Pennsylvania 7.87 cents/kWh against 8.13 nationally (EIA 2024)
Reviewed November 2026

What changes about chiller repair in Pennsylvania?

Chiller repair in Pennsylvania follows the same engineering as anywhere else, but four state conditions change what an owner has to plan for: how the Department of Labor and Industry’s vessel rules apply to the plant, whether a Philadelphia building is due for its energy tune-up, how hard the regional climate works the machine, and what the 2021 codes, in force statewide since January 1, 2026, ask of a replacement. The general faults, symptoms and repair methods are set out on the national chiller repair page; this page follows the Pennsylvania side of the decision.

Owners also bring an older plant stock than many states. Hospital and university central plants in Philadelphia’s University City and Pittsburgh’s Oakland, downtown office towers, and process plants built through the twentieth century still run machines charged with R-22 and R-123, next to newer units on R-134a and low-GWP refrigerants. That mix makes each repair a choice about refrigerant supply as well as parts.

Does Pennsylvania inspect chillers as pressure vessels?

Pennsylvania’s boiler and unfired pressure vessel regulations, 34 Pa. Code chapter 3a under the Boiler and Unfired Pressure Vessel Law, exclude air conditioner heat exchangers, which the rule names as chillers, when their design pressure is no more than 300 psi and the water they handle is at 210 degrees Fahrenheit or less. Most comfort-cooling machines fall inside that exclusion, so the chiller itself is usually outside the state’s inspection program. The vessels and exchangers around it are a separate question, and a repair that changes them can bring state requirements into the job.

How Pennsylvania’s vessel rules treat the equipment in a chiller plant
EquipmentStatus under 34 Pa. Code ch. 3aWhat it means for a repair
Chiller with design pressure up to 300 psi, water at 210 F or lessExcluded as an air conditioner heat exchangerRepairs follow the manufacturer, EPA refrigerant rules and the mechanical code
Machine outside those limits, such as a high-pressure refrigerant unitJudged against the chapter’s size and pressure exclusionsCheck the shell volume and design pressure on the nameplate before assuming it is excluded
Plate or shell-and-tube heat exchanger on the loopIn scope at 16 psi or more and 5 cubic feet or moreReplacement exchangers carry the code documentation the rule requires
Expansion tank or air separatorExcluded at 120 gallons of water or less; larger vessels judged against the other exclusions, including one for vessels operating at 15 psi or lessLarger tanks are part of the inspected plant
Small vessels and piping componentsExcluded within the volume and pressure pairs the rule lists, or at 6 inches inside diameter or lessStrainers and small filters rarely raise a state question
Steam boiler or hot water boiler on the same campusIn scopeInspected under the same law; covered on the boiler repair page

Labor and Industry’s guidance adds that work outside the boiler law may still fall under the Uniform Construction Code, which is how most chiller replacements are permitted. Paul Industries reads the nameplates on every vessel and exchanger in the plant during the first visit and records which ones the state inspects, so a repair that touches a heat exchanger or a large expansion tank is scoped with the right documents from the start. Boilers that share a central plant with the chillers are handled through boiler repair in Pennsylvania, and new code vessels for a plant through pressure vessel fabrication in Pennsylvania.

Philadelphia’s building tune-up law and the chiller plant

Philadelphia’s Building Energy Performance Program requires every non-residential building of 50,000 square feet or more to complete a tune-up of its energy systems, certify high performance, or obtain an exemption, and to repeat the report every five years. A tune-up reviews building systems and controls and corrects what is out of adjustment, and the chiller plant is where many of the findings sit: setpoints left at design values, sequences that run two machines where one would do, failed sensors, leaking valves and fouled tubes.

Philadelphia tune-up report deadlines in the current cycle
Building sizeTune-up report dueChiller plant work to schedule before the deadline
Over 200,000 square feetSeptember 30, 2026Repairs found in the current assessment, completed and documented before submission
100,000 to 200,000 square feetSeptember 30, 2027Condenser and evaporator tube condition, sensor calibration and sequence review during the 2027 shoulder season
70,000 to 100,000 square feetOctober 2, 2028Valve, pump and tower repairs planned into the 2027 to 2028 winter
50,000 to 70,000 square feetOctober 1, 2029Older plants: decide repair or replacement early so the tune-up describes the plant that will stay

An approved tune-up specialist, who must hold a Professional Engineer license or a CEM energy management credential and seven years of related experience, leads the assessment and signs the report. Missing the deadline carries a $2,000 fine plus $500 a day after the first 30 days. The corrections a tune-up identifies are mechanical work, and that is where Paul Industries comes in: repairing valves, actuators and sensors, restoring tube cleanliness, rebalancing condenser and chilled water flows, repairing tower fans and fill, and making the control changes the specialist recommends, with before and after readings for the report. Planning those repairs in the season before the deadline keeps the plant from being opened during peak summer load.

How the climate across Pennsylvania loads a chiller

The climate across Pennsylvania loads chillers unevenly, with the Delaware Valley carrying the hottest and most humid summers and the western and northern parts of the state running shorter, milder seasons. Philadelphia’s July normal high is 87.8 degrees Fahrenheit, while Pittsburgh’s is 83 degrees with a 63 degree low (NOAA, 1991 to 2020); Erie’s summers are cooler again near the lake, and the central valleys sit between them.

Chiller stress and repair emphasis by Pennsylvania region
RegionTypical chiller dutyFaults that show up mostRepair and service emphasis
Philadelphia and its suburbsLong humid summers; hospitals, labs and pharmaceutical plants with year-round loadHigh head pressure, condenser fouling, surge on light-load nightsTube cleaning, tower performance, condenser water reset
Lehigh Valley, Reading and LancasterProcess plants and warehouses with production-driven coolingGlycol and process water loop faults, pump and seal wearRepairs timed to production shutdowns
Harrisburg and Central PAGovernment, hospital and food plant coolingControls drift, aging starters, valve leakageControls repair and part-load sequencing
Pittsburgh and Southwest PAShorter season, long economizer hours, older campus plantsProblems at changeover between free cooling and mechanical cooling, idle-season corrosionChangeover sequences, layup and spring startup
Erie, State College and the northern tierMild summers, cold wintersFreeze damage in evaporators and outdoor pipingGlycol protection, draining, heat tracing

The east-west split changes which repairs pay back. In the Philadelphia region, condenser-side faults and high lift dominate, and a chiller condenser repair, from tube cleaning to retubing, often restores more capacity than compressor work. In the west, more hours are spent at part load or in free cooling, so controls, valves and the changeover sequence matter more, and machines that sit idle for months need proper layup to avoid corrosion and freeze damage.

Industrial chiller repair in Pennsylvania plants

Industrial chiller repair in Pennsylvania plants is planned around production, because a process chiller fault stops product rather than comfort. Pharmaceutical and cell therapy plants in Montgomery and Chester counties, snack, confectionery and dairy plants around Lancaster, York and Hershey, and chemical and metals plants in the west each tie their cooling to batches or lines, and each has its own records for a change to a validated or food-safety system.

As an industrial chiller repair service, Paul Industries diagnoses the fault from operating data before opening the machine, carries the likely parts into a planned shutdown, and returns process chillers to service with the test readings the plant’s quality system needs. Water chiller repair on a process loop often extends into the loop itself: heat exchanger fouling, pump wear and glycol strength. Chiller pump repair, seal replacement and alignment are part of the same visit, and single-line machines are covered further on the process chillers page.

Commercial chiller repair in Pennsylvania offices, hospitals and campuses

Commercial chiller repair in Pennsylvania offices, government buildings and campuses is booked into low-occupancy windows such as weekends, holidays and the spring and autumn months, when one machine down still leaves enough capacity, while hospital plants work under their own outage procedures because operating rooms, pharmacies and isolation rooms hold temperature and humidity limits. Before a hospital machine comes offline, Paul Industries confirms the remaining capacity against the expected load and arranges temporary cooling where redundancy is thin.

Data center chiller plants

Data center chillers in Pennsylvania are taken out of service singly, following a method of procedure the operator approves, and only after the remaining machines are shown to carry the hall. New campuses in the state are designed with long free-cooling hours, so repairs on those plants often focus on the economizer and changeover equipment rather than the compressor. Campus-scale work is described on data center cooling systems in Pennsylvania and data center mechanical contractor in Pennsylvania.

Which chiller faults come up most in Pennsylvania plants, and how are they repaired?

Pennsylvania chiller plants show a recurring set of faults, and each one points to a different repair: high head pressure and condenser fouling in the humid east, controls and changeover problems where free cooling runs for months, refrigerant leaks at aging joints and seals, and pump, valve and starter wear on machines that have run for decades. Paul Industries trends the operating data before opening a machine, so the repair goes to the component that is actually failing.

Symptoms, likely causes and the repair Paul Industries performs
SymptomLikely causesRepair
High head pressure trips on hot afternoonsFouled condenser tubes, weak tower, non-condensables, low condenser water flowTube cleaning, tower fan and fill repair, purge repair, flow rebalancing
Low evaporator pressure or freeze alarmsLow refrigerant charge, low chilled water flow, faulty expansion valve or sensorLeak search and repair, pump and strainer service, valve or sensor replacement
Rising refrigerant useLeaks at flanges, brazed joints, shaft seals or relief valvesLeak repair with verification tests and an updated leak rate record
Loud surge or vibrationHigh lift at light load, bearing wear, misalignment, worn vanesCondenser water reset, vibration analysis, bearing and alignment work
Short cycling or huntingPoor sequencing, oversized machine at low load, sensor driftControls repair, sequence changes, recalibration
Motor or starter faultsInsulation breakdown, failed contactors or drive componentsMegger testing, starter or drive repair, motor rewind or replacement
Low flow or noisy pumpsWorn impellers, failed seals, clogged strainers, cavitationChiller pump repair, seal replacement, alignment and strainer cleaning

The same diagnostic order applies whether the machine cools an operating room in Philadelphia or a product line in York: confirm the readings, test the simplest explanation first, and only then plan the invasive repair. That sequence keeps outage time short and stops a compressor from being opened when a tower or a strainer was the real problem.

Keeping cooling on while a Pennsylvania chiller is out of service

Keeping cooling on during a chiller repair in Pennsylvania depends on how much spare capacity the plant has on the worst afternoon of the repair window, so the first step is a load estimate for that window rather than an average day. In the Delaware Valley, a July or August outage leaves little margin; in Pittsburgh or Erie, the same outage in May or September often needs no temporary equipment at all.

Where margin is thin, Paul Industries connects a rental chiller to valved tees on the headers, or installs permanent connection points during the repair so later outages start with that work done. The temporary unit needs a power source, a level pad within hose reach and, if it is water-cooled, a condenser water arrangement. After the repair, the returning machine runs through a full afternoon peak before the rental is released, with its approach temperatures and pressures compared against the readings taken before the fault.

Refrigerant rules behind chiller refrigeration repair in Pennsylvania

Federal rules set the refrigerant requirements behind chiller refrigeration repair in Pennsylvania, and the one that changed daily practice is EPA’s leak repair rule, in force since January 1, 2026 for machines holding 15 pounds or more of an HFC. Each refrigerant addition triggers a leak rate calculation; a comfort-cooling chiller above 10 percent a year, a commercial refrigeration system above 20 percent, or industrial process refrigeration above 30 percent must be repaired within 30 days, or 120 days when a process shutdown is needed, and verified by testing.

Older refrigerants sit under the HCFC phaseout. R-22 production and import ended on January 1, 2020, though existing machines can run on reclaimed supply, and import allowances for R-123 end in 2030. New comfort-cooling chillers installed since January 1, 2025 use refrigerants with a global warming potential below 700. For a Pennsylvania campus with a mixed fleet, the practical result is a ranking: which machines to keep tight and running, which to retrofit, and which to replace first. Paul Industries logs leak rates, repairs and verification tests together for each machine and prices refrigerant separately from parts and labor.

Can chillers provide heating in a Pennsylvania building?

Chillers can provide heating in a Pennsylvania building when they are heat recovery or heat pump machines, which deliver the heat removed from the chilled water loop to a hot water loop instead of rejecting it to a tower. Buildings with simultaneous heating and cooling, such as hospitals, labs and data halls next to offices, gain the most, because the same compressor work serves both loads through the long Pennsylvania heating season.

A heat recovery machine needs a hot water loop designed for lower supply temperatures than a steam or high-temperature boiler system, so retrofits usually involve coil and control changes as well as the chiller. Paul Industries repairs existing heat recovery machines and, when a replacement is due, prices a heat recovery option alongside a like-for-like unit, so the owner of an aging boiler and chiller plant can compare the two.

What chiller service in Pennsylvania includes

Chiller service in Pennsylvania under a Paul Industries contract includes seasonal startup and shutdown, operating log review, leak rate records, oil, refrigerant and vibration analysis, tube cleaning and eddy current testing at intervals set by the machine’s duty, and the towers, pumps and controls that serve the chillers. Chiller maintenance in Pennsylvania has two seasonal points that matter most: spring startup before the first humid week in the east, and autumn layup before the first hard freeze in the west and north.

Refrigerant purity is checked against AHRI 700 where reclaimed refrigerant is in use, and the service file is kept so it doubles as evidence for a Philadelphia tune-up report or an insurer’s inspection. Programs are written as service contracts, and towers are kept in condition through cooling tower repair; plate and shell-and-tube units on the same loop go to heat exchanger repair.

Chiller removal and replacement under the 2021 Pennsylvania codes

Chiller removal and replacement in Pennsylvania now proceeds under the 2021 International Codes, which took effect statewide through the Uniform Construction Code on January 1, 2026, and in Philadelphia under the city’s own Title 4 adoption of the same model codes. A replacement brings refrigerant recovery from the old machine, rigging, structural and electrical checks, machinery room requirements drawn from ASHRAE 15 for the new refrigerant, piping changes, startup and permits.

Rigging is often the hardest part in older Pennsylvania buildings, where plant rooms sit in basements or on roofs of buildings put up long before today’s equipment sizes. Machines may have to come out in sections, and the new unit may arrive knocked down for assembly in the room. The HVAC chiller replacement cost is driven by those access conditions as much as by tonnage, so Paul Industries surveys the route, the structure and the electrical service before pricing. Piping modifications around the new machine are covered on process piping in Pennsylvania.

What drives chiller repair cost in Pennsylvania?

Chiller repair cost in Pennsylvania depends first on what failed: a bad sensor, a leaking valve, worn bearings, a failed motor winding or a damaged tube bundle sit at very different price points. Around that core, the tonnage and compressor type, the pounds of refrigerant to recover and replace, how hard the plant room is to reach, whether rental cooling is needed, and whether the work lands in July or in March, or just ahead of a Philadelphia tune-up deadline, set the rest of the number.

Electricity prices shape the repair or replace choice. Pennsylvania’s average industrial price was 7.87 cents per kilowatt-hour in 2024, below the national 8.13 (EIA), so efficiency alone pays back more slowly than in higher-priced states. As an illustration with stated assumptions, a 400-ton machine that saves 0.20 kilowatts per ton across 2,000 equivalent full-load hours saves 160,000 kilowatt-hours a year, about $12,600 at that average price. Paul Industries runs the same calculation on the owner’s tonnage, run hours and actual rate, and adds the refrigerant outlook and leak history before recommending repair or replacement.

Who handles chiller repair in Pennsylvania?

Paul Industries handles chiller repair in Pennsylvania as an East Coast contractor that was formerly based in the state and is now headquartered at 256 Shore Drive in Kilmarnock, Virginia, and takes work in every part of the state: Pittsburgh and the Southwest, Erie, State College and the northern tier, Harrisburg and Central Pennsylvania, Lancaster and Reading, Scranton, Wilkes-Barre and the Lehigh Valley, and Philadelphia with its Montgomery, Chester and Bucks county suburbs and King of Prussia. As a chiller repair company it covers centrifugal, screw and scroll machines of the major makes, along with the towers, pumps, piping and controls around them.

Paul Industries brings the same chiller repair service to the headquarters state, described on chiller repair in Virginia, and to the neighboring state on chiller repair in New Jersey. Owners who ask who works on chillers from the compressor to the cooling tower get one answer and one contract.

Chiller repair and replacement from Paul Industries in Pennsylvania

Paul Industries diagnoses, repairs, overhauls, retrofits, maintains, supplies and installs chillers for Pennsylvania plants, hospitals, universities, data centers and commercial buildings, and documents each job for EPA leak records, state vessel questions and Philadelphia tune-ups. For a repair, send a nameplate photo, the refrigerant type and charge, fault codes and a few weeks of trend data; for a replacement study, add the load profile, electric rate and plant room access. Call 201-450-8280 or request a quote. The wider list of services for the state is on the Pennsylvania page.

Standards referenced: Pennsylvania Boiler and Unfired Pressure Vessel Law (35 P.S. 1331.1 et seq.) · 34 Pa. Code ch. 3a · Pennsylvania Uniform Construction Code (34 Pa. Code ch. 401-405) · Philadelphia Building Construction and Occupancy Code (Title 4) · Philadelphia Building Energy Performance Program · EPA Emissions Reduction and Reclamation rule, 40 CFR 84.106 · EPA Technology Transitions rule · Clean Air Act Section 608 · ASHRAE 15 · AHRI 700

Frequently asked questions

Which firm handles chiller repair in Philadelphia, from Center City to the Navy Yard?

Paul Industries handles chiller repair in Philadelphia, including Center City office towers, University City hospitals and labs, and plants and campuses at the Navy Yard and in the Northeast. Philadelphia buildings of 50,000 square feet or more also face tune-up deadlines, so repairs are often scheduled to close the findings of a tune-up assessment. Send the make, model, refrigerant and recent alarm history to scope the work.

Does Paul Industries offer chiller repair in Pittsburgh and Southwest Pennsylvania?

Yes. Paul Industries offers chiller repair in Pittsburgh, from Downtown and Oakland to plants along the Allegheny, Monongahela and Ohio rivers and in Washington and Westmoreland counties. Western Pennsylvania’s milder summers mean longer free-cooling seasons, so changeover sequences, valve and controls faults and idle-season layup are common work, along with compressor, tube and refrigerant repairs.

Who repairs chillers in Allentown, Bethlehem, Reading and Lancaster?

Paul Industries provides chiller repair in Allentown, Bethlehem and Easton, Reading, and chiller repair in Lancaster and York, where process plants, warehouses and hospitals run chillers tied to production or patient care. Process machines are repaired during planned shutdowns with parts staged in advance, and glycol strength, pump seals and heat exchangers on the loop are checked at the same visit.

Is there a contractor for chiller repair in Harrisburg and Central Pennsylvania?

Paul Industries takes chiller repair in Harrisburg, Hershey, Carlisle, State College and across Central Pennsylvania, for government buildings, hospitals, universities and food plants. Central plants in the region often serve campuses with mixed heating and cooling loads, which makes heat recovery a practical option when a machine reaches the end of its life.

Does a chiller in Pennsylvania need a state inspection certificate?

Most do not, because 34 Pa. Code 3a.3 excludes chillers with a design pressure of no more than 300 psi that handle water at 210 degrees Fahrenheit or less. Exchangers holding 5 cubic feet or more that run at 16 psi or above, larger expansion tanks and boilers in the same plant can be in scope. Paul Industries records each vessel’s nameplate data so the owner knows which ones the state inspects.

Do Philadelphia tune-up rules require a chiller to be replaced?

The tune-up program centers on reviewing systems and controls and correcting what is out of adjustment, with a report every five years for buildings of 50,000 square feet or more. Findings usually call for repairs, recalibration and sequence changes rather than new equipment. When an assessment points to a failing machine, Paul Industries prices repair and replacement side by side so the owner can decide before the report is due.

What happens if a Philadelphia building misses its tune-up deadline?

The city fines $2,000 plus $500 a day after the first 30 days. Buildings over 200,000 square feet report by September 30, 2026, and smaller ones follow in 2027, 2028 and 2029. Plant repairs found in the assessment take time to schedule outside peak season, so starting the chiller work early keeps the report on time.

Does a chiller replacement in Pennsylvania need a permit?

A replacement is permitted work under the Uniform Construction Code, which adopted the 2021 International Codes on January 1, 2026, administered by the municipality or its code agency, and in Philadelphia by Licenses and Inspections under Title 4. Paul Industries prepares the mechanical submittal, coordinates inspections and closes the permit with the startup and test records.

What does EPA's leak repair rule ask of a Pennsylvania chiller owner?

Since January 1, 2026, machines holding 15 pounds or more of an HFC need a leak rate calculation each time refrigerant is added. Comfort cooling above 10 percent a year, commercial refrigeration above 20 percent or industrial process refrigeration above 30 percent must be repaired within 30 days, or 120 days with a process shutdown, then verified. Paul Industries keeps those records with each repair.

Should a Pennsylvania hospital keep repairing its R-123 centrifugal chillers?

Often for now, with a plan. Import allowances for R-123 end in 2030, after which machines rely on reclaimed and stockpiled supply, so keeping them tight protects both the machine and the refrigerant. A hospital with several R-123 units benefits from a replacement sequence that retires the worst machine first, ideally timed to the low-load months. Paul Industries prices that sequence alongside each major repair.

What is chiller condenser repair, and when is it needed?

Chiller condenser repair covers tube cleaning, plugging failed tubes, retubing the bundle, repairing waterbox coatings and gaskets, and on air-cooled machines, coil and fan repair. It is needed when condenser approach temperatures climb, head pressure rises or eddy current testing finds wall loss. In the Philadelphia region’s humid summers, fouled condenser tubes are a frequent cause of high-pressure trips.

How is a chiller laid up for winter in Erie and the northern tier?

Idle machines have their evaporators and outdoor piping drained or protected with glycol, because ice in the tubes can split them and flood the refrigerant side with water. Oil heaters usually stay energized, and the condenser water side is drained where the tower is outdoors. In spring Paul Industries refills, checks the charge and safeties, and runs the machine under load before the first warm spell.

What does chiller removal involve in an older Pennsylvania building?

Removal starts with refrigerant recovery and records, then disconnecting power and piping, and rigging the machine out through the route available, sometimes in sections through a basement areaway or by crane from a roof. Paul Industries surveys the route, structure and electrical service first, so the old unit comes out and the new one goes in on a planned sequence.

What does HVAC chiller replacement cost depend on in Pennsylvania?

Tonnage and machine type set the equipment price, but access, rigging, electrical upgrades, piping changes, refrigerant recovery, temporary cooling and permit requirements often move the total as much. Pennsylvania’s industrial power price of 7.87 cents per kilowatt-hour (EIA, 2024) makes the efficiency payback slower than in costlier states, so refrigerant risk and reliability weigh heavily. Paul Industries gives a budget range from comparable scope, then a firm price after a site survey.

Can an old chiller be converted to recover heat for a building?

Some can be paired with a heat exchanger to use condenser heat for preheating, but a true heat recovery machine is usually a replacement selected for the higher condensing temperature. The hot water loop may need lower-temperature coils and new controls. Paul Industries assesses the loads, prices both the add-on and the replacement route, and installs whichever the owner chooses.

Which details speed up pricing for a chiller fault at a Pennsylvania site?

Useful details include a photo of the nameplate, the refrigerant and its charge, fault codes from the controller, a few weeks of trended pressures, temperatures and amps, the most recent service visit notes and any refrigerant added this year. Philadelphia buildings should add the tune-up findings if an assessment has been done. Paul Industries plans the diagnostic visit from that information and prices parts, refrigerant and labor separately.

Who works on chillers at Pennsylvania food and pharmaceutical plants during production?

Paul Industries works on chillers at pharmaceutical plants in Montgomery and Chester counties and at food plants around Lancaster, York and Hershey, planning repairs into shutdowns and leaving the change and test records the plant’s quality system needs. Where a process cannot stop, temporary chillers are connected so the line keeps its cooling while the machine is repaired.

How often should a Pennsylvania chiller have eddy current testing?

The interval follows the machine’s history: owners test condenser and evaporator tubes more often on machines with heavy run hours, open towers with fouling history or past tube failures, and less often on clean closed loops. Trending results from test to test shows how fast wall loss is advancing and when retubing or replacement should be budgeted. Paul Industries schedules testing during planned shutdowns and keeps the results with the machine’s service file.

Have a chiller to repair somewhere in Pennsylvania?

Send the chiller make, model and serial number, refrigerant, alarm history and recent logs. Call 201-450-8280 or request a quote.