Paul Industries engineers, pipes, fills, tests and maintains data center liquid cooling in New Hampshire: coolant distribution units, cold plate and rear door loops, row manifolds, and the dry coolers and glycol circuits that reject rack heat to Granite State air. Warm-water loops suit this state unusually well, because a loop supplied near 90 F can shed its heat outdoors without a chiller for more than nine hours in ten in Manchester and Concord, and the heat that comes back from the racks is warm enough to put to work through a six-month heating season.

Request a quote or call 201-450-8280

Headquarters 256 Shore Drive, Kilmarnock, Virginia
Dry cooler weather Air at or below 79.6 F for 92.9% of Manchester hours (2021-2025)
Summer dew point At or above 60 F for about 1,400 Manchester hours a year
Hydronic test 1.5 x design pressure, 100 psi minimum, 15 minutes (2024 IMC 1208.1)
Exempt vessels Water-containing vessels at 125 psig or less (RSA 157-A:6)
Reviewed November 2026

Data center liquid cooling in New Hampshire, from research clusters to colocation cages

Data center liquid cooling in New Hampshire is moving into rooms that were built for air: university research clusters, colocation suites taking denser tenants, and engineering and simulation rooms inside manufacturers. Few of those rooms have spare chiller capacity or floor space, so liquid cooling projects here often begin as a retrofit of one or two rows inside a room that has to keep running.

The basic mechanics of cold plates, CDUs, secondary loops and immersion are set out on the national data center liquid cooling page. This page covers what changes in New Hampshire: how warm the facility water can run on this state’s weather, how to keep an outdoor loop from freezing at minus 29 F, how to keep cold plates dry through a humid Merrimack Valley summer, where the rack heat can go in winter, and which state rules touch the vessels and boilers in a heat-reuse loop.

Where does dense computing run in New Hampshire?

Dense computing in New Hampshire runs in university research clusters, in a handful of colocation suites around Manchester and Bedford, and in enterprise rooms at manufacturers, hospitals and engineering firms. Two research systems show the trend clearly as market facts. The University System of New Hampshire runs Premise, a condo-funded high performance cluster for its researchers whose published GPU inventory includes recent accelerator generations, and Dartmouth’s Discovery cluster in Hanover lists 128 nodes and 6,712 CPU cores, with GPU partitions that include current data center accelerators.

Those accelerators push rack heat well past what a raised floor and perimeter CRAH units were sized for, which is why the first liquid-cooled rows in New Hampshire tend to appear in research and campus rooms. Colocation operators follow when tenants ask for dense cabinets, and manufacturers follow when simulation and inspection systems outgrow their server closets. Campus and research room work is also covered on the research labs and universities page.

A first liquid cooling phase in a New Hampshire room is usually sized for more than the first racks. Headers, valved branches, the facility water connection and the outdoor dry cooler pad are built for the full row count the owner expects over several years, while CDUs and manifolds are added as racks arrive. That approach keeps later phases out of the ceiling and off the roof, where winter work is slow and a crane pick in January depends on the weather, and it lets each new row connect during a short planned window instead of a long outage. Paul Industries writes the phasing plan with the owner’s IT team so cooling capacity always lands ahead of the hardware.

How warm can a New Hampshire facility water loop run on dry coolers?

A New Hampshire facility water loop can run on dry coolers alone for most of the year at any of the warmer ASHRAE liquid cooling classes, and the warmer the class, the closer it gets to all year. The table assumes a dry cooler sized for about a 10 degree approach, so the outdoor air has to sit 10 F below the supply temperature for the dry cooler to carry the full load.

Share of 2021 to 2025 hours when dry coolers alone can hold each ASHRAE W class supply limit (10 F approach)
W class (supply limit)ManchesterConcordPortsmouthLebanonBerlin
W17 (62.6 F)50.6%55.4%52.6%55.9%63.2%
W27 (80.6 F)80.6%84.4%84.7%84.7%89.3%
W32 (89.6 F)92.9%94.6%95.3%94.6%96.9%
W40 (104 F)99.8%99.9%99.9%100%100%
W45 (113 F)100%100%100%100%100%

Two decisions follow from the table. First, a W32 loop, which most current cold plate servers accept, needs mechanical trim cooling for roughly 410 to 620 hours a year in the southern half of the state and about 270 in Berlin; that trim can come from an existing chilled water plant through a heat exchanger, an adiabatic boost on the dry cooler, or a small dedicated chiller. Second, a W40 loop in Manchester sees about 19 hours a year above 94 F, so an owner who can run warmer water can plan the outdoor plant around dry coolers with no compressors at all.

Paul Industries sizes the trim to the actual hours rather than to a full-capacity chiller. Where the building already has a chilled water plant, a plate heat exchanger tied into the chilled water return often covers the warm afternoons for very little first cost; where it has none, a small air-cooled chiller with a free cooling coil does the job.

Freeze protection on the outdoor loop: can liquid cooling freeze at minus 29 F?

Liquid cooling can freeze in New Hampshire wherever water sits outdoors, in an unheated penthouse or in a roof dunnage run, because the state’s coldest hours reach minus 12 F in Manchester, minus 20 F in Lebanon and minus 29 F in Berlin. The racks themselves stay warm inside the building; the risk is the outdoor loop, the dry cooler coils and any piping that stops flowing during an outage or a low-load night.

The usual answer is a heat exchanger that separates an outdoor glycol loop from an indoor water loop, so the rack-side coolant stays plain treated water or the manufacturer’s specified fluid while the outdoor side carries propylene glycol. A 40 percent propylene glycol mix freezes near minus 8 F, enough for the Seacoast and most of the Merrimack Valley; Berlin and the North Country call for about 50 percent, which freezes near minus 29 F. Glycol costs pump energy and heat transfer every hour, so Paul Industries sets the concentration from the site’s record rather than adding margin out of habit.

Controls carry the rest of the protection. Dry cooler fans stage down and bypass valves open so the loop does not overcool on a January night, pumps keep a minimum flow through outdoor coils, heat tracing covers exposed dead ends and instrument lines, and low-temperature alarms are tested before winter. Berlin’s record includes a 492-hour run at or below freezing, so North Country loops are also given a drain-down plan for long outages.

Keeping cold plates dry through a humid Merrimack Valley summer

Cold plates stay dry in a New Hampshire summer when the rack-side supply temperature is held above the dew point of the room air, because any surface colder than the dew point collects condensation. Outdoor dew points here run higher than many buyers expect: Manchester recorded a dew point of 60 F or more for about 1,400 hours a year from 2021 to 2025, and Portsmouth for about 1,540.

Summer moisture at five New Hampshire stations, 2021 to 2025
StationHours per year with dew point at or above 60 FHours per year at or above 70 FJuly mean dew point
Manchester1,40618562.0 F
Concord1,40420362.1 F
Portsmouth1,53621462.6 F
Lebanon1,35717961.8 F
Berlin9184458.2 F

A well-run room controls its own dew point through the air system, and the ASHRAE recommended envelope tops out at a 59 F dew point, but a room with leaky doors, an economizer bringing in outdoor air, or a humidifier fault can drift above it. The CDU therefore holds its secondary supply a few degrees above the measured room dew point and alarms if the margin closes. Facility water piping that runs cold, such as a trim heat exchanger fed from chilled water, is insulated with a vapor retarder, which the 2024 International Mechanical Code requires in Section 1206.11 through its rule against condensation on pipe exteriors.

Data center waste heat recovery through a New Hampshire heating season

Data center waste heat recovery fits New Hampshire because Manchester’s monthly mean temperature stays below 50 F from November through April, and Berlin’s from October through April, so a building near a liquid-cooled room needs heat for half the year or more. Liquid cooling makes data center waste heat far easier to capture than air cooling, because the heat leaves the racks in water rather than in mixed room air.

Data center waste heat temperature from cold plate loops

Data center waste heat temperature from a cold plate loop is set by the supply class and the flow: return water typically runs 10 to 18 F above supply, so a W32 loop returns water around 100 to 105 F and a W40 or W45 loop returns it well above 110 F. That is warm enough to preheat domestic hot water, ventilation air or a low-temperature hot water heating loop directly, and a heat pump can lift it to the 140 F to 160 F range that older radiators and coils need.

Where liquid cooling heat goes in a New Hampshire building
Heat userTemperature it needsHow the rack heat reaches itSeason
Ventilation air preheatAny water above outdoor airGlycol runaround coil in the outdoor air intakeOctober to May
Domestic hot water preheatAbove incoming cold waterPlate heat exchanger ahead of the water heaterAll year
Low-temperature hot water heatingAbout 100 to 130 F supplyDirect exchange or a small heat pump boostHeating season
Conventional hot water heatingAbout 140 to 180 FWater-to-water heat pumpHeating season
Snow melt and sidewalk heatingLow-grade warm glycolSeparate glycol loop and exchangerWinter storms

Campus hot water networks are a natural home for this heat, and one is being built in the Upper Valley: Dartmouth is converting its Hanover campus from steam to hot water heating as part of a decarbonization program of roughly $500 million announced in 2024, because hot water can take low-grade heat from sources such as geo-exchange and heat pumps that a steam system cannot use. Any campus or building owner moving to lower-temperature hot water creates a place for rack heat to go.

Vessels and boilers in a heat-reuse loop under RSA 157-A

The state’s boiler statute touches a heat-reuse loop through the boilers that back it up. RSA 157-A:6 exempts water-containing vessels at 125 psig or less, including expansion tanks where air acts only as a cushion, along with vessels at 15 psig or less and pump-pressurized tanks, so most expansion and buffer tanks on a liquid cooling loop fall outside the certificate program. Hot water heating boilers that carry the building when rack heat is short stay inside the program: under RSA 157-A:8 they need a certificate inspection every two years. Boiler work in the same loop is covered by boiler repair in New Hampshire.

Leak protection and coolant care in a New Hampshire room

Leak protection for a liquid-cooled row in New Hampshire starts with the piping layout and ends with a coolant sampling routine that runs for the life of the loop. Manifolds and quick disconnects sit where a drip falls into a tray rather than onto power distribution, leak detection cable runs under every manifold and along pipe routes over equipment, and isolation valves at each row let one rack or one branch be shut without draining the room.

Coolant care matters more in a cold climate than many owners expect, because the outdoor glycol loop and the indoor water loop age differently. Glycol breaks down slowly with heat and oxygen and loses its inhibitors, so its concentration, pH and inhibitor level are checked at least each autumn before the cold arrives; the rack-side loop is sampled for conductivity, pH, biological growth and particulates on the schedule the server maker sets. Paul Industries sets up the sampling plan at turnover, keeps spare filters and coolant on hand for the site, and services CDUs, strainers and dry coolers under a maintenance agreement where the owner wants one.

Rear door heat exchangers on an existing New Hampshire chilled water plant

Rear door heat exchangers give many New Hampshire rooms a first step toward liquid cooling without touching the servers, because they run on water from the existing chilled water plant and remove heat at the back of each rack. The doors need water above the room dew point, a dedicated branch with balancing valves and a condensate plan for humid summer days, and they work best where the building plant already runs a raised supply temperature. Paul Industries pipes, balances and tests rear doors and later converts the same branch to serve CDUs when the racks change.

Space, power and piping for CDUs in Manchester mills and Nashua office parks

CDUs in New Hampshire buildings go where the floor, the power and the pipe routes allow, and the state’s converted mill buildings and suburban office parks each bring their own limits. A Manchester Millyard room may have generous ceiling height but older timber or concrete floors with modest load ratings; a Nashua or Salem office-park room may have a modern slab but a low ceiling crowded with ductwork and cable tray.

Paul Industries surveys the structure, the electrical service and the routes before choosing between in-row CDUs, which sit in the rack line and need floor capacity there, and facility CDUs in a mechanical room, which need a longer secondary loop. Supply and return headers are sized for the full planned row count with valved, capped branches for future racks, and drip trays and leak detection cable run under manifolds and over any equipment below. The building’s main mechanical scope, from electrical rooms to rooftop dunnage, sits with data center mechanical contractors in New Hampshire, and the piping methods follow the same practice as process piping in New Hampshire.

Immersion cooling asks still more of the floor, because a filled tank concentrates heavy fluid on a small footprint. In mill buildings Paul Industries checks the floor rating before a tank is placed and often spreads the load on steel frames or places tanks on grade. Immersion systems are covered on the data center immersion cooling page.

Testing and filling a new loop to the 2024 International Mechanical Code

A new liquid cooling loop in New Hampshire is tested under the 2024 International Mechanical Code, which the State Building Code adopted on July 1, 2026: Section 1208.1 calls for a hydrostatic test at one and one-half times the maximum system design pressure, at least 100 psi, held for at least 15 minutes. The 100 psi floor applies even to low-pressure secondary loops, so CDUs, cold plates and any component with a lower rating are isolated or left unconnected during the test.

After the test, the loop is flushed at velocity through temporary strainers and bypasses until the strainers come out clean, then filled with treated water or the specified coolant, vented at every high point and sampled for chemistry before IT equipment is connected. Paul Industries records test pressures and hold times, flush results, fill volumes, coolant concentration and initial water quality for the owner and the IT vendor’s warranty file. Integrated testing of the CDUs, controls and outdoor plant is covered under data center commissioning in New Hampshire.

Liquid cooling energy on New Hampshire power prices

Liquid cooling energy matters more in New Hampshire than in most states because commercial electricity cost 21.40 cents per kWh in the first eight months of 2026, against a US average of 14.04, according to the EIA. A chiller running at 0.6 kW per ton to serve 500 kilowatts of rack heat would draw about 85 kilowatts, roughly $160,000 a year at that average if it ran every hour; a W32 loop on dry coolers in Concord leaves the chiller off for about 95 percent of hours.

The power that remains goes to CDU pumps and dry cooler fans. Twenty-five kilowatts of pumps and fans running all year use 219,000 kWh, about $46,866 at the 2026 commercial average, so variable speed pumps, fan staging on supply temperature, and low-pressure-drop manifolds and strainers all earn their cost here. Paul Industries builds the energy comparison for each site on the owner’s own tariff.

Data center liquid cooling cost in New Hampshire: what drives the price

Data center liquid cooling cost in New Hampshire is driven by the number of racks and their heat load, the CDU type and redundancy, the length and material of the secondary and facility piping, the outdoor heat rejection and freeze protection, any heat-reuse connection, the structural and electrical work the room needs, and how much of the job happens around live equipment. Paul Industries prices each project from a survey of the room and the plant, then states a budget range and a firm price once the scope is set.

A data center liquid cooling system for the first rows in an existing room usually costs most in the facility water connection and the outdoor plant, and least in the rack manifolds; later phases cost less because the headers, valved branches and heat rejection are already in place. Supply-only CDUs and manifolds, design-build of the whole loop and complete installation of an engineer’s design are each available, and owners often mix them across phases.

Who builds data center liquid cooling loops in New Hampshire?

Paul Industries builds data center liquid cooling loops in New Hampshire, from the first cold plate row in a Hanover research room to dry cooler plants for colocation suites in Manchester and Bedford. The work covers survey and design, CDUs and manifolds, secondary and facility piping, dry coolers and glycol systems, heat recovery connections, testing, flushing, filling and long-term coolant care.

Headquartered at 256 Shore Drive, Kilmarnock, Virginia, Paul Industries takes liquid cooling work across New Hampshire and New England and in all 50 states; the data center liquid cooling in Virginia page covers its headquarters state. Neighboring pages cover data center liquid cooling in Massachusetts and data center liquid cooling in Connecticut, and the room and plant around the loop are covered by data center cooling in New Hampshire. Every Paul Industries service in the state is listed on the New Hampshire hub.

Liquid-cooled rows from Paul Industries across New Hampshire

Paul Industries brings liquid cooling into New Hampshire rooms on a plan that fits the building: the warmest water the racks allow, dry coolers that carry nearly the whole year, glycol where the cold reaches, condensation margins proven in August, and rack heat sent to a building that needs it in January. Share the rack plan, room drawings and plant data, and Paul Industries returns a phased scope and price. Call 201-450-8280 or request a quote.

Standards referenced: ASHRAE TC 9.9 liquid cooling (W) classes · ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments · New Hampshire State Building Code, RSA 155-A (2024 International Mechanical Code) · 2024 International Mechanical Code, Sections 1206.11 and 1208.1 · RSA 157-A (New Hampshire boilers and pressure vessels), Sections 157-A:6 and 157-A:8

Frequently asked questions

Who provides liquid cooling for data centers in Durham and the Seacoast?

Paul Industries provides liquid cooling for data centers and research rooms in Durham, Portsmouth, Dover and the rest of the Seacoast, from the first cold plate row to dry cooler plants. Portsmouth recorded about 1,540 hours a year with a dew point of 60 F or more from 2021 to 2025, the moistest of the five stations reviewed, so CDU supply margins and pipe insulation get particular attention there. Call 201-450-8280 or request a quote.

Can Paul Industries pipe liquid-cooled racks into a Manchester or Nashua colocation suite?

Paul Industries pipes liquid-cooled racks into colocation suites and enterprise rooms in Manchester, Bedford, Nashua and Merrimack, working with the operator’s change windows and tenant rules. Typical work is a facility water connection from the building plant, in-row or facility CDUs, row manifolds with valved branches, leak detection and a dry cooler loop on the roof or pad, all tested before any tenant equipment is connected.

Who installs liquid cooling for research computing in Hanover and Lebanon?

Paul Industries installs liquid cooling for research and hospital computing rooms in Hanover, Lebanon and the Upper Valley. Lebanon’s coldest hour in the 2021 to 2025 record was minus 20 F, so outdoor loops there carry propylene glycol behind a heat exchanger, and campus owners moving to hot water heating can take the rack heat into their networks. Paul Industries designs the loop, the outdoor plant and the heat recovery connection together.

Does Paul Industries take liquid cooling work in Concord, Keene and the Monadnock region?

Paul Industries takes liquid cooling work in Concord, Keene, Peterborough, Jaffrey and the Monadnock region, including state, hospital, college and manufacturing computer rooms. Concord’s record supports a W32 loop on dry coolers for about 95 percent of hours, so most projects pair a dry cooler with a small trim source for summer afternoons. Call 201-450-8280 or request a quote.

How warm can facility water run before a New Hampshire loop needs a chiller?

Facility water can run at about 104 F, the W40 limit, before a New Hampshire loop needs any chiller at all in most places, because with a 10 degree dry cooler approach Manchester saw only about 19 hours a year above 94 F from 2021 to 2025. At the W32 limit of 89.6 F a loop needs trim cooling for roughly 410 to 620 hours a year in the south. The rack manufacturer’s supply limit decides the class.

What is the data center waste heat temperature from a W32 loop?

A W32 loop returns water at roughly 100 to 105 F, since return water typically runs 10 to 18 F above a supply near 89.6 F. That heat can preheat ventilation air or domestic water directly, feed a low-temperature heating loop, or be lifted by a water-to-water heat pump for older radiators and coils. Warmer classes such as W40 and W45 return heat above 110 F and make reuse simpler.

Can rack heat preheat ventilation air in a New Hampshire building?

Rack heat can preheat ventilation air through a glycol runaround coil in the outdoor air intake, and in New Hampshire that coil has work from October to May. Manchester’s January mean temperature is 28.6 F, so even modest return water temperatures lift incoming air a long way and cut the heating plant’s load. Paul Industries sizes the coil, the glycol loop and the controls so the room’s cooling always takes priority.

Do expansion tanks on a liquid cooling loop need a New Hampshire boiler certificate?

Expansion tanks on a liquid cooling loop are usually exempt from New Hampshire’s certificate program, because RSA 157-A:6 exempts water-containing vessels at 125 psig or less, including those with an air cushion, and vessels at 15 psig or less. Boilers are different: a hot water heating boiler that backs up a heat-reuse loop needs a certificate inspection every two years under RSA 157-A:8, and operating it without one is unlawful under 157-A:10.

How is a new liquid loop pressure tested under the 2024 mechanical code?

A new liquid loop is pressure tested hydrostatically at one and one-half times its maximum design pressure, never below 100 psi, for at least 15 minutes, under Section 1208.1 of the 2024 International Mechanical Code that New Hampshire adopted on July 1, 2026. CDUs, cold plates and lower-rated components are isolated first. Paul Industries records the test and then flushes, fills and samples the loop before racks connect.

What happens to an outdoor liquid cooling loop during a winter power outage?

An outdoor loop that stops flowing in a New Hampshire winter starts losing heat to the air at once, which is why outdoor circuits carry propylene glycol matched to the site’s coldest hour and pumps sit on UPS or generator power. Paul Industries also gives North Country sites a drain-down procedure for long outages, since Berlin’s record includes 492 straight hours at or below freezing.

Does the rack-side loop need glycol if only the outdoor loop sees winter?

The rack-side loop usually runs on treated water or the server maker’s specified fluid, because a heat exchanger keeps it indoors and away from freezing air, and glycol would cut heat transfer at the cold plates. The outdoor loop carries the glycol. Paul Industries confirms the rack-side fluid against the IT vendor’s warranty terms before the first fill.

What should a New Hampshire owner look for among data center liquid cooling companies?

A New Hampshire owner comparing data center liquid cooling companies should look for one contract that covers design, CDUs, piping, outdoor heat rejection, freeze protection, testing and coolant care, with documented pressure tests, flush records and water chemistry at turnover. Paul Industries delivers all of that under one schedule and one set of records, and states its price in budget and firm stages. Call 201-450-8280 or request a quote.

Can immersion tanks go into a converted New Hampshire mill building?

Immersion tanks can go into a converted mill building once the floor rating is checked, because a filled tank concentrates heavy dielectric fluid on a small footprint. Paul Industries reviews the structure, spreads load on steel frames where needed or places tanks on grade, and plans fluid delivery, containment and heat rejection piping around the building’s columns and openings.

How much electricity does a dry cooler liquid loop use compared with a chiller in New Hampshire?

A dry cooler liquid loop uses a fraction of a chiller’s electricity in New Hampshire. Serving 500 kilowatts of rack heat, a chiller at 0.6 kW per ton draws about 85 kilowatts, roughly $160,000 a year at the 2026 commercial average if it ran all year, while a W32 dry cooler loop in Concord keeps the chiller off about 95 percent of the time and spends its power on pumps and fans.

How is a liquid cooling retrofit staged in an occupied New Hampshire room?

A liquid cooling retrofit in an occupied New Hampshire room is staged so that headers, valves and the outdoor plant are built and tested before any rack is touched. Facility water tie-ins are made in planned windows with redundancy confirmed, branches are added row by row, and each new row is flushed, filled and proven before servers move onto it. Air cooling for the rest of the room keeps running throughout.

What turnover documents does Paul Industries hand over for a New Hampshire liquid loop?

Paul Industries hands over as-built drawings, pressure test records with pressures and hold times, flush and strainer records, fill volumes and coolant concentration, initial water chemistry, CDU and dry cooler startup reports, control sequences and alarm setpoints, and a coolant sampling schedule. Those records support the IT vendor’s warranty and give the next shift a clear picture of the loop.

What information starts a New Hampshire liquid cooling quote?

A New Hampshire liquid cooling quote starts with the rack count and heat load per rack, the server maker’s supply temperature and fluid limits, room and roof drawings, the existing chilled water plant data, electrical service details and the room’s outage windows. With that, Paul Industries returns a phased scope, a budget range and then a firm price. Call 201-450-8280 or request a quote.